SECO NDARY TEST S ETU PS
RECOMMENDED TROU BLES HOOTING TOO LS
78
1VLG5000 17 C
Local HMI of 640 series
The LHMI supports the engineer during the relay’s testing, commissioning and troubleshoot-
ing activities. The information, traditionally accessible through different paths within the
menu structure, is provided in collectively grouped and visualized format.
Figure 121: Home page for Testing and Commissioning pages
Checking GOOSE data
On the
GOOSE Receiving
page, check the GOOSE data that the relay subscribes from the
Ethernet network. The left side of this page shows a list of devices that send GOOSE mes-
sages to the relay. These devices that publish data for the relay are defined in the relay con-
figuration. The right side of the page shows the GOOSE data the relay receives from the net-
work. The data set consists of value and quality attributes. The received data has status
indicators where green means all OK, yellow warning and red error.
Figure 122: GOOSE Receiving Page