ETHER NET NETWOR K VER IFICATIO N
INTERCO NNECTIO NS
1VLG5000 17 C
17
Check if No GOOSE / SMV alarm is reported by the receiver protection relays.
Figure 25: GOOSE / SMV alarm is activated on a configurable LED
Check the Measurements view on the voltage receiver protection relays if voltage values are
not in brackets.
Brackets indicate an invalid or a questionable measurement due to, for example, a
time synchronization error.
Figure 26: Measurements view, voltage receiver protection relay is not synchronized with the
Master clock
Figure 27: Measurements view, voltage receiver protection relay is synchronized with the Mas-
ter clock
Frequency information in the Measurements view is in brackets if no voltage is meas-
ured by the protection relay