SECO NDARY TESTING O F PROTECTIO N R ELAYS
SECO NDARY TEST S ETU PS
1VLG5000 17 C
71
Step 3/3
Simulate high currents on the current sensor input via the front voltage outputs 1, 2.
–
U1 = U2 with 180° phase shift (symmetrical source).
Simulate voltage on the voltage sensor input via the front voltage output U4, N.
–
U4 =
𝑈𝑛
√3
Figure 110: Setting of high voltage analogue outputs in the Test Universe program
Figure 111: Phasor diagram on the protection relay’s WebHMI
Figure 112: Measurements view