The start and trip LEDs are configured via the disturbance recorder.
The yellow and red status LEDs are configured in the disturbance
recorder function, DRPRDRE, by connecting a start or trip signal
from the actual function to a BxRBDR binary input function block
using the PCM600 and configure the setting to
Off
,
Start
or
Trip
for
that particular signal.
Table 11:
Ready LED (green)
LED state
Description
Off
Auxiliary supply voltage is disconnected.
On
Normal operation.
Flashing
Internal fault has occurred.
Table 12:
Start LED (yellow)
LED state
Description
Off
Normal operation.
On
A protection function has started and an indication message is displayed.
•
The start indication is latching and must be reset via communication or
by pressing
.
Flashing
A flashing yellow LED has a higher priority than a steady yellow LED.
The IED is in test mode and protection functions are blocked.
•
The indication disappears when the IED is no longer in test mode and
blocking is removed.
Table 13:
Trip LED (red)
LED state
Description
Off
Normal operation.
On
A protection function has tripped and an indication message is displayed.
•
The trip indication is latching and must be reset via communication or
by pressing
.
Alarm indicators
The 15 programmable three-color LEDs are used for alarm indication. An individual
alarm/status signal, connected to any of the LED function blocks, can be assigned to
one of the three LED colors when configuring the IED.
1MRK 505 291-UEN A
Section 5
Local human-machine interface
81
Application manual
Содержание Relion REQ650
Страница 1: ...Relion 650 series Breaker protection REQ650 Application manual ...
Страница 2: ......
Страница 20: ...14 ...
Страница 26: ...20 ...
Страница 48: ...42 ...
Страница 82: ...76 ...
Страница 90: ...84 ...
Страница 160: ...154 ...
Страница 178: ...172 ...
Страница 264: ...258 ...
Страница 288: ...282 ...
Страница 302: ...296 ...
Страница 330: ...324 ...
Страница 338: ...332 ...
Страница 339: ...333 ...