REQ650 (A01)
Z
SC
: Low
Earth fault
Line protection zone 1 reach
IEC10000154-1-en.vsd
IEC10000154 V1 EN
Figure 20:
Fault for step 2 setting
Proposed current setting is therefore 1200 A.
1.
Set
DirMode2
to
Reverse
.
2.
Set
IN2>
to
120%
of
IBase
(1200 A primary current).
3.
Set
t2
to
0.4 s
.
3.1.7.4
Calculating settings for step 3
The current setting should be chosen in line with normal setting principles in the
system. To detect high resistive faults, a current setting of about 100 A will detect
earth-faults with a fault resistance up to about 800 Ω. Proposed current setting is
therefore 100 A.
1.
Set
DirMode3
to
Non-directional
.
2.
Set
IN3>
to
10%
of
IBase
(100 A primary current).
3.
Set
t3
to
1.5 s
.
1MRK 505 291-UEN A
Section 3
REQ650 setting examples
57
Application manual