BLOCKOFF
Used to Unblock the Auto-Reclosing function when it has gone to Block due to
activating input BLKON or by an unsuccessful Auto-Reclose attempt if the setting
BlockByUnsucCl
is set to
On
. Input is normally set to FALSE.
RESET
Used to Reset the Auto-Recloser to start condition. Possible Thermal overload Hold
and so on will be reset. Positions, setting
On
-
Off
and so on will be started and checked
with set times. Input is normally set to FALSE.
Recommendations for output signals
SETON
Indicates that the auto-reclose function is switched ON and operative.
BLOCKED
Indicates that the auto-reclose function is temporarily or permanently blocked.
ACTIVE
Indicates that STBRREC is active, from start until end of reclaim time.
INPROGR
Indicates that a sequence is in progress, from start until reclosing command.
UNSUCCL
Indicates unsuccessful reclosing.
CLOSECB
Connect to a binary output for circuit-breaker closing command.
READY
Indicates that the Auto-reclosing function is ready for a new and complete reclosing
sequence. It can be connected to the zone extension of a line protection should
extended zone reach before automatic reclosing be necessary.
1PT1
Indicates that 1-phase automatic reclosing is in progress. It is used to temporarily
block an earth-fault and/or pole disagreement function during the 1-phase open
interval
3PT1, 3PT2, 3PT3, 3PT4 and 3PT5
Indicates that three-phase automatic reclosing shots 1-5 are in progress. The signals
can be used as an indication of progress or for own logic.
Section 10
1MRK 505 291-UEN A
Control
224
Application manual
Содержание Relion REQ650
Страница 1: ...Relion 650 series Breaker protection REQ650 Application manual ...
Страница 2: ......
Страница 20: ...14 ...
Страница 26: ...20 ...
Страница 48: ...42 ...
Страница 82: ...76 ...
Страница 90: ...84 ...
Страница 160: ...154 ...
Страница 178: ...172 ...
Страница 264: ...258 ...
Страница 288: ...282 ...
Страница 302: ...296 ...
Страница 330: ...324 ...
Страница 338: ...332 ...
Страница 339: ...333 ...