Substation A
Substation B
Z
lineAB,1
(pos. seq)
Z
lineAB,0
(zero seq)
Z
lineBC,1
(pos. seq)
Z
lineBC,0
(zero seq)
U
0A
U
0B
3I
0
Phase to earth fault
R
N
Z
T,1
(pos. seq)
Z
T,0
(zero seq)
Source impedance
Z
sc
(pos. seq)
en06000654.vsd
IEC06000654 V1 EN
Figure 62:
Equivalent of power system for calculation of setting
The residual fault current can be written:
phase
0
1
0
f
3U
3I
2 Z
Z
3 R
=
×
+
+ ×
EQUATION1948 V1 EN
(Equation 34)
Where
U
phase
is the phase voltage in the fault point before the fault
Z
1
is the total positive sequence impedance to the fault point. Z
1
= Z
sc
+Z
T,1
+Z
lineAB,1
+Z
lineBC,1
Z
0
is the total zero sequence impedance to the fault point. Z
0
= Z
T,0
+3R
N
+Z
lineAB,0
+Z
lineBC,0
R
f
is the fault resistance.
The residual voltages in stations A and B can be written:
(
)
0 A
0
T ,0
N
U
3I
Z
3R
=
×
+
EQUATION1949 V1 EN
(Equation 35)
OB
0
T ,0
N
lineAB,0
U
3I (Z
3R
Z
)
=
×
+
+
EQUATION1950 V1 EN
(Equation 36)
Section 6
1MRK 505 291-UEN A
Current protection
126
Application manual
Содержание Relion REQ650
Страница 1: ...Relion 650 series Breaker protection REQ650 Application manual ...
Страница 2: ......
Страница 20: ...14 ...
Страница 26: ...20 ...
Страница 48: ...42 ...
Страница 82: ...76 ...
Страница 90: ...84 ...
Страница 160: ...154 ...
Страница 178: ...172 ...
Страница 264: ...258 ...
Страница 288: ...282 ...
Страница 302: ...296 ...
Страница 330: ...324 ...
Страница 338: ...332 ...
Страница 339: ...333 ...