AutoCont and tAutoContWait, Automatic continuation to the next shot if
the CB is not closed within the set time
The normal setting is
AutoCont
=
Off
. The
tAutoContWait
is the length of time
STBRREC waits to see if the breaker is closed when
AutoCont
is set to
On
. Normally
the setting can be
tAutoContWait
=
2 s
.
10.4
Apparatus control
10.4.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Bay control
QCBAY
-
-
Local remote
LOCREM
-
-
Local remote control
LOCREMCTRL
-
-
10.4.2
Application
The apparatus control is a function for control and supervising of circuit breakers,
disconnectors, and earthing switches within a bay. Permission to operate is given after
evaluation of conditions from other functions such as interlocking, synchrocheck,
operator place selection and external or internal blockings.
The complete apparatus control function is not included in this
product, and the information below is included for understanding of
the principle for the use of QCBAY, LOCREM, and LOCREMCTRL
for the selection of the operator place.
gives an overview from what places the apparatus control function receive
commands. Commands to an apparatus can be initiated from the Control Centre (CC),
the station HMI or the local HMI on the IED front.
Section 10
1MRK 505 291-UEN A
Control
228
Application manual
Содержание Relion REQ650
Страница 1: ...Relion 650 series Breaker protection REQ650 Application manual ...
Страница 2: ......
Страница 20: ...14 ...
Страница 26: ...20 ...
Страница 48: ...42 ...
Страница 82: ...76 ...
Страница 90: ...84 ...
Страница 160: ...154 ...
Страница 178: ...172 ...
Страница 264: ...258 ...
Страница 288: ...282 ...
Страница 302: ...296 ...
Страница 330: ...324 ...
Страница 338: ...332 ...
Страница 339: ...333 ...