handled if the recording functions do not have proper settings. The goal is to optimize
the settings in each IED to be able to capture just valuable disturbances and to
maximize the number that is possible to save in the IED.
The recording time should not be longer than necessary (
PostFaultrecT
and
TimeLimit
).
•
Should the function record faults only for the protected object or cover more?
•
How long is the longest expected fault clearing time?
•
Is it necessary to include reclosure in the recording or should a persistent fault
generate a second recording (
PostRetrig
)?
Minimize the number of recordings:
•
Binary signals: Use only relevant signals to start the recording that is, protection
trip, carrier receive and/or start signals.
•
Analog signals: The level triggering should be used with great care, since
unfortunate settings will cause enormously number of recordings. If nevertheless
analog input triggering is used, chose settings by a sufficient margin from normal
operation values. Phase voltages are not recommended for trigging.
Remember that values of parameters set elsewhere are linked to the information on a
report. Such parameters are, for example, station and object identifiers, CT and VT
ratios.
12.8
Measured value expander block MVEXP
12.8.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Measured value expander block
MVEXP
-
-
12.8.2
Application
The current and voltage measurements functions (CVMMXN, CMMXU, VMMXU
and VNMMXU), current and voltage sequence measurement functions (CMSQI and
VMSQI) and IEC 61850 generic communication I/O functions (MVGGIO) are
provided with measurement supervision functionality. All measured values can be
supervised with four settable limits, that is low-low limit, low limit, high limit and
high-high limit. The measure value expander block (MVEXP) has been introduced to
be able to translate the integer output signal from the measuring functions to 5 binary
signals, that is below low-low limit, below low limit, normal, above high-high limit or
above high limit. The output signals can be used as conditions in the configurable
logic.
Section 12
1MRK 505 291-UEN A
Monitoring
276
Application manual
Содержание Relion REQ650
Страница 1: ...Relion 650 series Breaker protection REQ650 Application manual ...
Страница 2: ......
Страница 20: ...14 ...
Страница 26: ...20 ...
Страница 48: ...42 ...
Страница 82: ...76 ...
Страница 90: ...84 ...
Страница 160: ...154 ...
Страница 178: ...172 ...
Страница 264: ...258 ...
Страница 288: ...282 ...
Страница 302: ...296 ...
Страница 330: ...324 ...
Страница 338: ...332 ...
Страница 339: ...333 ...