Figure 40:
Fault current: I
F
100
Is
IP
IBase
>>=
×
EQUATION1147 V3 EN
(Equation 5)
6.1.3.2
Meshed network with parallel line
In case of parallel lines, the influence of the induced current from the parallel line to
the protected line has to be considered. One example is given in figure
where the
two lines are connected to the same busbars. In this case the influence of the induced
fault current from the faulty line (line 1) to the healthy line (line 2) is considered
together with the two through fault currents I
fA
and I
fB
mentioned previously. The
maximal influence from the parallel line for the IED in figure
at the C point with the C breaker open.
A fault in C has to be applied, and then the maximum current seen from the IED (I
M
)
on the healthy line (this applies for single-phase-to-earth and two-phase-to-earth
faults) is calculated.
Section 6
1MRK 505 291-UEN A
Current protection
88
Application manual