MeasType
: Selection of discrete Fourier filtered (
DFT
) or true RMS filtered (
RMS
)
signals.
RMS
is used when the harmonic contents are to be considered, for example in
applications with shunt capacitors.
Operation
: The protection can be set to
Off
or
On
2ndHarmStab
: Operate level of 2nd harmonic current restrain set in % of the
fundamental current. The setting range is
5 - 100
% in steps of 1%. Default setting is
20%.
U
ref
I
dir
IEC09000636_1_vsd
1
2
2
3
4
IEC09000636 V1 EN
Figure 46:
Directional function characteristic
1. RCA = Relay characteristic angle 55°
2. ROA = Relay operating angle 80°
3. Reverse
4. Forward
Section 6
1MRK 505 291-UEN A
Current protection
96
Application manual