shortest possible time difference, the operation time of protections, breaker opening
time and protection resetting time must be known. These time delays can vary
significantly between different protective equipment. The following time delays can
be estimated:
Protection operate time:
15-60 ms
Protection resetting time:
15-60 ms
Breaker opening time:
20-120 ms
The different characteristics are described in the Technical Manual (TM).
tx
: Definite time delay for step
x
. The definite time
tx
is added to the inverse time when
inverse time characteristic is selected.
INx>
: Operate residual current level for step
x
given in % of
IBase
.
kn
: Time multiplier for inverse time delay for step
n
.
IMinn
: Minimum operate current for step
n
in % of
IBase
. Set
IMinn
below
INx>
for
every step to achieve ANSI reset characteristic according to standard. If
IMinn
is set
above
INx>
for any step then signal will reset at current equals to zero.
tnMin
: Minimum operating time for inverse time characteristics. At high currents the
inverse time characteristic might give a very short operation time. By setting this
parameter the operation time of the step
n
can never be shorter than the setting.
IEC09000164-2
Operate time
Current
tx
tnMin
IMinn
IEC09000164 V2 EN
Figure 59:
Minimum operate current and operate time for inverse time
characteristics
1MRK 505 291-UEN A
Section 6
Current protection
119
Application manual
Содержание Relion REQ650
Страница 1: ...Relion 650 series Breaker protection REQ650 Application manual ...
Страница 2: ......
Страница 20: ...14 ...
Страница 26: ...20 ...
Страница 48: ...42 ...
Страница 82: ...76 ...
Страница 90: ...84 ...
Страница 160: ...154 ...
Страница 178: ...172 ...
Страница 264: ...258 ...
Страница 288: ...282 ...
Страница 302: ...296 ...
Страница 330: ...324 ...
Страница 338: ...332 ...
Страница 339: ...333 ...