input channels on the binary input output module (BIO) have individual settings for
debounce time, oscillation count and oscillation time. The values can be changed in
the local HMI and PCM600 under
Main menu/Configuration/I/O modules
The debunce time should be set to the same value for all channels on
the board
The setting isindividual for all input channels on the binary input
output module (BIO), that is, if changes of the limits are made for
inputs not connected to the pulse counter, it will not influence the
inputs used for pulse counting.
13.2
Energy calculation and demand handling EPTMMTR
13.2.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Energy calculation and demand
handling
ETPMMTR
Wh
IEC10000169 V1 EN
-
13.2.2
Application
Energy calculation and demand handling function ETPMMTR is intended for
statistics of the forward and reverse active and reactive energy. It has a high accuracy
basically given by the measurements function (CVMMXN). This function has a site
calibration possibility to further increase the total accuracy.
The function is connected to the instantaneous outputs of (CVMMXN) as shown in
figure
.
P
Q
STACC
RSTACC
RSTDMD
TRUE
FALSE
FALSE
CVMMXN
IEC09000106.vsd
ETPMMTR
P_INST
Q_INST
IEC09000106 V1 EN
Figure 108:
Connection of energy calculation and demand handling function
ETPMMTR to the measurements function (CVMMXN)
Section 13
1MRK 505 291-UEN A
Metering
284
Application manual
Содержание Relion REQ650
Страница 1: ...Relion 650 series Breaker protection REQ650 Application manual ...
Страница 2: ......
Страница 20: ...14 ...
Страница 26: ...20 ...
Страница 48: ...42 ...
Страница 82: ...76 ...
Страница 90: ...84 ...
Страница 160: ...154 ...
Страница 178: ...172 ...
Страница 264: ...258 ...
Страница 288: ...282 ...
Страница 302: ...296 ...
Страница 330: ...324 ...
Страница 338: ...332 ...
Страница 339: ...333 ...