Headline
Explanation
GOOSE is configured on a disabled port
At least one of the access points configured for
GOOSE is disabled. The port can be disabled
either through changing the access point
operation to off or by unchecking the GOOSE
protocol from the access point in the Ethernet
configuration in PCM600 or LHMI.
Please enable GOOSE on access points:
AP_FRONT, AP_1
LDCM not running the application image
<slot number> is running the factory image
instead of the application image. The factory
image is older and does not contain the latest
updates and fixes.
Please reboot the IED. If the problem persists
update the LDCM firmware or replace the board.
LDCM version is not accepted
<device name> firmware version <version
string> is not accepted. The minimum accepted
version is <version string>.
Please update the LDCM firmware or replace the
board.
12.3
Repair instruction
IP8767-1 v1
M11764-2 v2
Never disconnect the secondary connection of a current transformer
circuit without short-circuiting the transformer’s secondary
winding. Operating a current transformer with the secondary
winding open will cause a massive potential build up that may
damage the transformer and may cause injuries to humans.
Never connect or disconnect a wire and/or a connector to or from a
IED during normal service. Hazardous voltages and currents are
present that may be lethal. Operation may be disrupted and IED and
measuring circuitry may be damaged.
M11764-10 v1
An alternative is to open the IED and send only the faulty circuit board to ABB for
repair. When a printed circuit board is sent to ABB, it must always be placed in a
metallic, ESD-proof, protection bag. The user can also purchase separate
replacement modules.
Strictly follow the company and country safety regulations.
M11766-4 v2
Most electronic components are sensitive to electrostatic discharge and latent
damage may occur. Please observe usual procedures for handling electronics and
also use an ESD wrist strap. A semi-conducting layer must be placed on the
workbench and connected to earth.
Section 12
1MRK 506 383-UEN A
Troubleshooting
188
Line distance protection REL650 2.2 IEC
Commissioning manual
Содержание REL650 series
Страница 1: ...RELION 650 SERIES Line distance protection REL650 Version 2 2 Commissioning manual...
Страница 2: ......
Страница 24: ...18...
Страница 28: ...22...
Страница 38: ...32...
Страница 54: ...48...
Страница 58: ...52...
Страница 178: ...172...
Страница 182: ...176...
Страница 188: ...182...
Страница 196: ...190...
Страница 206: ...200...
Страница 207: ...201...