Expected result: the protection function does not issue either start or trip.
GUID-7C9F1163-0186-41DA-9D5F-DDA589323B9F v1
After each test it is possible to download and study the related disturbance
recording.
IEC10000142-1-en.vsd
0
1
2
COMMON TRIP COMMAND (trip)
-1
0
1
TRIPZ1 (tripZone1)
0
1
2
TRIPZ2 (tripZone2)
0
1
2
START (start)
0
1
2
GENMODE (generatorMode)
0
0.5
1
1.5
2
2.5
3
3.5
4
4.5
5
-1
0
1
time in seconds
→
MOTMODE (motorMode)
IEC10000142 V1 EN-US
Figure 16:
Boolean output signals for the injected current with two
components: a 50 Hz current component and a 49.5 Hz current
component
9.3.4
Automatic switch onto fault logic ZCVPSOF
M13850-2 v9
Prepare the IED for verification of settings outlined in Section
.
The automatic switch onto fault logic function ZCVPSOF is checked using
secondary injection tests. ZCVPSOF is activated either by the external input
BC
or
by the internal DLD. FUFSPVC is done with a pre-fault condition where the phase
voltages and currents are at zero. A three-phase fault with zero impedance and a
three-phase fault with an impedance corresponding to the whole line is applied.
This fault shall cause an instantaneous trip and result in a
TRIP
indication.
1MRK 506 383-UEN A
Section 9
Testing functionality by secondary injection
Line distance protection REL650 2.2 IEC
99
Commissioning manual
Содержание REL650 series
Страница 1: ...RELION 650 SERIES Line distance protection REL650 Version 2 2 Commissioning manual...
Страница 2: ......
Страница 24: ...18...
Страница 28: ...22...
Страница 38: ...32...
Страница 54: ...48...
Страница 58: ...52...
Страница 178: ...172...
Страница 182: ...176...
Страница 188: ...182...
Страница 196: ...190...
Страница 206: ...200...
Страница 207: ...201...