1.
Simulate normal operating conditions with the three-phase currents in phase
with their corresponding phase voltages and with all of them equal to their
rated values.
2.
Slowly decrease the measured voltage in one phase until the BLKU signal
appears.
3.
Record the measured voltage and calculate the corresponding negative-
sequence voltage according to the equation (observe that the voltages in the
equation are phasors):
3
2
1
2
⋅
+
⋅
+ ⋅
U
U
U
U
L
L2
L3
=
a
a
EQUATION707 V2 EN-US
(Equation 92)
Where:
U
L1
, U
L2
and U
L3
IEC00000275 V1 EN-US
are the measured phase voltages
2
3
3
1
0, 5
2
j
a
e
j
p
×
= ×
= -
+
.
IECEQUATION00022 V2 EN-US
4.
Compare the result with the set value of the negative-sequence operating
voltage (consider that the set value
3U2>
is in percentage of the base voltage
UBase
).
5.
and
. Then slowly increase the measured current in one phase
until the BLKU signal disappears.
6.
Record the measured current and calculate the corresponding negative-
sequence current according to the equation (observe that the currents in the
equation are phasors):
2
1
2
3
2
3
L
L
L
I
I
a I
a I
×
=
+
×
+ ×
IECEQUATION00021 V1 EN-US
(Equation 93)
Where:
1
2
3
L
L
L
I
I and I
,
IECEQUATION00020 V1 EN-US
are the measured phase currents
2
3
3
1
0, 5
2
j
a
e
j
p
×
= ×
= -
+
.
IECEQUATION00022 V2 EN-US
7.
Compare the result with the set value of the negative-sequence operating
current. Consider that the set value
3I2<
is in percentage of the base current
IBase
.
Section 9
1MRK 506 383-UEN A
Testing functionality by secondary injection
132
Line distance protection REL650 2.2 IEC
Commissioning manual
Содержание REL650 series
Страница 1: ...RELION 650 SERIES Line distance protection REL650 Version 2 2 Commissioning manual...
Страница 2: ......
Страница 24: ...18...
Страница 28: ...22...
Страница 38: ...32...
Страница 54: ...48...
Страница 58: ...52...
Страница 178: ...172...
Страница 182: ...176...
Страница 188: ...182...
Страница 196: ...190...
Страница 206: ...200...
Страница 207: ...201...