1.
Check that the auto recloser function is operative, for example by making an
auto reclosing shot.
Keep the CB simulator BR closed. Remove the
CBREADY
signal by opening
SRY.
2.
Apply a fault and thereby a START signal.
3.
Check that no auto reclosing takes place.
Checking the influence of synchrocheck (at three-phase reclosing)
M12400-161 v10
1.
Check that the auto recloser is operative, for example, by making a three-
phase reclosing shot with the synchrocheck SESRSYN conditions fullfilled.
Set the SESRSYN function to
Off
to eliminate the signal connected to input
signal SYNC.
2.
Apply a fault causing three-phase trip and thereby a
START
and a
TR3P
signal
to the auto recloser.
3.
Wait for the
tSync
time-out limit.
Check that no reclosing is made.
Checking the response when auto recloser is
Off
M12400-173 v7
Procedure
1.
Check that the auto recloser is operative, for example by making a reclosing
shot.
Set the autoreclosing operation to
Off
, for example by external control.
The output
READY
shall be low, and
PREP3P
shall be high.
2.
Apply a single phase fault and thereby a
START
signal.
3.
Check that a definitive three phase trip and no auto reclosing takes place.
Restoring equipment
M12400-190 v6
After the tests, restore the equipment to normal or desired state. Check the
following items in particular:
1.
Check the operation counters.
Reset the counters to zero, if that is the user's preference. The counter reset
function is found on the local HMI under
Main menu/Reset/Reset counters/
AutoRecloser79,5(0–>1)/SMBRREC(79,5(0–>1)):x
2.
Restore settings that may have been modified for the tests back to normal.
3.
Disconnect the test switch, circuit breaker simulating arrangement and test
circuits.
Reconnect any links or connection terminals, which may have been opened
for the tests.
4.
Reset indications, alarms and disturbance recordings.
Clearing of the disturbance report can be done via the Disturbance Handling
in PCM600 or the local HMI.
Section 9
1MRK 506 383-UEN A
Testing functionality by secondary injection
146
Line distance protection REL650 2.2 IEC
Commissioning manual
Содержание REL650 series
Страница 1: ...RELION 650 SERIES Line distance protection REL650 Version 2 2 Commissioning manual...
Страница 2: ......
Страница 24: ...18...
Страница 28: ...22...
Страница 38: ...32...
Страница 54: ...48...
Страница 58: ...52...
Страница 178: ...172...
Страница 182: ...176...
Страница 188: ...182...
Страница 196: ...190...
Страница 206: ...200...
Страница 207: ...201...