ABB REL 356 Current Differential Protection
3-2
Settings and Application
Table 3-1. Setting Table Continued
Setting
Format
Min
Max
Step
Units
Notes
C0
Zero sequence coefficient
C1
Positive sequence coefficient
C2
Negative sequence coefficient
ALDT
Enable automatic LDT compensation
LDFL
Select LDT leader/follower mode
LDT
Local delay time setting
msec
UNID
Unit ID
OTH
Operating threshold
KBPS
Communication speed (56 or 64 kbps)
6
TTRP
Transfer trip
Note 1:
Note 3:
These settings have a "OUT" option for disabling a corresponding function.
Note 4:
The impedance setting. The setting ranges shown are for 5 A ct. The displayed setting range is multiplied by 5 if a 1 A ct is
used (CTYP = 1).
Note 5:
9600 bps Audio Tone option.
Note 2:
These settings have a "BLK" option for disabling a corresponding function.
Note 6:
56/64 kbps Digital Communication option.
Note 7:
Only if optional extended output is included.
Note 8:
Only if optional backup system is included.
Name
Z2P
ohms
4, 8
Zone 2 phase distance setting in ohms
BKUP
8
Backup Protection Enable
LPBK
Loopback Test
RLSD
dBm
5
Receiver level signal detect setting
XMTR
dBm
5
Modem transmitter level setting
XPUD
ohms
Primary Ohms per unit
DTYP
Selection of distance units for XPUD setting
PANG
deg
Positive sequence line impedance angle
GANG
deg
Zero sequence line impedance angle
ZR
Line impedance ratio (Z0L/Z1L)
LOPB
8
Loss-of-potential blocking selection
FDOP
Directional Overcurrent Phase
FDOG
Directional Overcurrent Ground
DIRU
Directional Unit Selection
IOM
1, 8
Medium set ground current pickup value in amps
TOG
sec
2, 8
Timer for Ground Overcurrent Unit
T2P
sec
2, 8
Zone 2 phase time delay in seconds
XCLK
6
Source of Transmit Clock
TDES
Trip Desensitizing
XX.XX
XX.XX
XX.XX
XX.XX
IN/OUT
MI/KM
XXXX
XXXX
XXX.X
YES/NO
IN/OUT
IN/OUT
ZSEQ/NSEQ
YES/NO
-43/-33/-26/-16
XXXX
X.XXX
INT/EXT
X.XXX
X.XXX
X.XXX
YES/NO
LEAD/FOLO
XXX.X
X.XXX
XXXX
64/56
IN/OUT
X.XXX
0.01
0.1
0.01
0.01
1
1
0.1
0.05
0.05
0.05
0.1
1
0.05
2
0.001
0.1 X P.U.
5.000
5.000
5.000
32.0
1 5
3.950
50.00
-1
1.500
90
90
10.0
10.0
9.99
2.99
10 X P.U.
0.01
0.5
0.10
0.00
0.000
0.000
0.000
0.000
0.0
0
-15
0.100
10
10
0.1
1.1 X P.U.
For 5 A relay. Setting and step are a factor of 5 lower for 1 A relay.
A
Содержание REL 356
Страница 23: ...ABB REL 356 Current Differential Protection 1 10 Product Overview and Specifications ...
Страница 83: ...ABB REL 356 Current Differential Protection 3 36 Settings and Application ...
Страница 127: ...ABB REL 356 Current Differential Protection 5 28 Testing ...
Страница 186: ...LINE SECTIONALIZING USING A PLC AND ABB PROTECTIVE RELAY Page 49 of 53 ...
Страница 187: ...LINE SECTIONALIZING USING A PLC AND ABB PROTECTIVE RELAY Page 50 of 53 ...
Страница 188: ...LINE SECTIONALIZING USING A PLC AND ABB PROTECTIVE RELAY Page 51 of 53 ...
Страница 189: ...LINE SECTIONALIZING USING A PLC AND ABB PROTECTIVE RELAY Page 52 of 53 ...