MODEM COMMUNICATION TO ABB RELAYS
Page 24 of 47
in that a dumb terminal interface is able to attach and display the device settings/metering parameters….
The REL512 sends out (via its RD line) a time/date ASCII string every minute for display on the attached
device. This fact is very critical in that the modem or device attached must be able to tolerate this string.
Additionally, the REL 3XX products or the TPU/DPU 2000R, GPU2000R or DPU1500R communication
ports are slave only in their protocol design. The port only responds to requests. The REL512 differs in
that it sends out at time string without any prompting to the attached device.
The REL512 also uses a numeric character or alphabet character to move through its menus. The other
devices discussed in the other examples use protocols and do not respond to the attached device strings.
The REL512 will respond to each character. As shown in this example, the attached device (in this case
the modem) must be able to tolerate this operational characteristic.
The REL512 has settings capabilities configurable and viewable via its front com port (which is a DCE
RS232 port) or its front panel interface. Any dumb terminal emulator is able to connect to the front port
and synchronize with the unit to allow visualization of the REL512 parameters. Within this example, two
US ROBOTIC model 002806 (V.EVERYTHING modem using trellis technology encoding [which differs
from the QAM encoding]). As illustrated in Figure 33, the modems are configured via a point to point
connection. The REL512 ASCII protocol is not addressable and therefore cannot be multi-dropped
unless port switch devices are added to the system. The steps to establish communications are:
1.
Connect the correct cable between the REL512 front and the modem.
2.
Connect the correct cable between the PC executing the HYPERTERMINAL program (in this
case the operating system used is WINDOWS 95).
3.
Parameterization of the REL512 front port communication parameters.
4.
Parameterization of the HYPERTERMINAL settings.
5.
Parameterization of the USROBOTICS modems using its particular AT command set.
6.
Execution of the connectivity procedure to establish communications.
As illustrated in Figure 33, the topology of the REL512 interconnection with the HYPERTERMINAL
software is illustrated. Please note on the diagram, the appropriate cables used to connect the device. In
this example, the communication handshaking cannot be used since RTS/CTS, DCD, DSR, DTR signals
are not supported on the REL512 front communication RS232 port.
19200 Baud
REL512 MENU ASCII
REL 512
Public Switched
Telephone Network - ANALOG LINE
Personal Computer With
An Operating System
Offering a HYPERTERMINAL
Utility
10 Bit Dial Up MODEM
10 Bit Dial Up MODEM
Auto- Answer
Enabled
Example Cable 4-
Figure 5..
Example Cable 6 or 7
Figures 12 or 13.
ABB
ABB
ABB
ABB
ABB
LOCAL
LOCATION
REMOTE
LOCATION
Figure 33. Modem Connection between a REL512 Front Port and Hyperterminal
Configuration Software
Содержание REL 356
Страница 23: ...ABB REL 356 Current Differential Protection 1 10 Product Overview and Specifications ...
Страница 83: ...ABB REL 356 Current Differential Protection 3 36 Settings and Application ...
Страница 127: ...ABB REL 356 Current Differential Protection 5 28 Testing ...
Страница 186: ...LINE SECTIONALIZING USING A PLC AND ABB PROTECTIVE RELAY Page 49 of 53 ...
Страница 187: ...LINE SECTIONALIZING USING A PLC AND ABB PROTECTIVE RELAY Page 50 of 53 ...
Страница 188: ...LINE SECTIONALIZING USING A PLC AND ABB PROTECTIVE RELAY Page 51 of 53 ...