MODEM COMMUNICATION TO ABB RELAYS
Page 10 of 47
PLC Cable
Male Cable Gender
( 9 Pin Connector)
Modem Cable
Male Cable Gender
(25 Pin Connector)
DTE
DCE
2
3
4
6
5
7
8
9
3 RCD
2 TXD
7 GND
4 RTS *
5 CTS *
6 DSR *
20 DTR *
RCD
TXD
DSR
DTR
GND
RTS *
CTS *
(Signal Flow Direction Denoted By Arrow)
*OPTIONAL
DEPENDENT ON
MODEM CONTROL
LINE CONFIGURATION
Figure 15. Cable 8: PLC Cable Connectivity to a Modicon PLC with Handshaking
Disabled on the PLC and Modem Side.
AT Command Set
Within these examples, a Hayes Compatible external telephone modem from 3Com and ZOOM is used.
The command sets and S Registers differ slightly based upon the chip set used. For example, the ZOOM
modem uses a chipset from LUCENT TECHNOLOGIES. The description of the command set is available
from the internet web-site www.lucent.com. The 3Com modem has their command set available on the
Internet web-site
www.3com.com
: The AT “&” commands are usually the same for both manufacturers,
However, the definition of the AT “X” (Where X may be a letter or a “\” or && and a letter) commands vary
widely between the manufacturers. Also the AT”S” (S register commands) register definitions vary widely
between the two manufacturers.
US Robotics (3COM) 56 K (V.90 or X2) Sportster Faxmodem
The Sportster FAXMODEM is an external modem. This modem allows visualization of a variety of
parameters allowing for visual troubleshooting in the event of trouble. The Sportster also has a set of
dipswitches allowing for quick configuration without connection of a “Terminal Emulator” to configure the
unit through “AT commands. Please refer to the web-site documents for a more complete explanation of
configuration strings.
Prior to configuring the modem, attach the proper cable between the terminal emulator and the modem.
One Should Type “AT” (without the quotation marks) and depress the enter key. The modem shall echo
back an “OK” to acknowledge the communication. It is recommended that the dipswitches for this unit be
set as follows:
1: Down – Data Terminal Ready Overriden (EXCEPT IF USING THE BIRT)
2: Down – Numeric Results Code Displayed
3: Down – Display Results Code
4: UP – Echo OFFLINE Commands
5: Dependent upon application – AUTO ANSWER
6 Down- Carrier Detect Override (EXCEPT IF USING THE BIRT)
7: UP – Load NVRAM DEFAULTS
8: Down – Smart Mode Operation
If the modem does not answer, please check the terminal emulator settings to be the following:
Содержание REL 356
Страница 23: ...ABB REL 356 Current Differential Protection 1 10 Product Overview and Specifications ...
Страница 83: ...ABB REL 356 Current Differential Protection 3 36 Settings and Application ...
Страница 127: ...ABB REL 356 Current Differential Protection 5 28 Testing ...
Страница 186: ...LINE SECTIONALIZING USING A PLC AND ABB PROTECTIVE RELAY Page 49 of 53 ...
Страница 187: ...LINE SECTIONALIZING USING A PLC AND ABB PROTECTIVE RELAY Page 50 of 53 ...
Страница 188: ...LINE SECTIONALIZING USING A PLC AND ABB PROTECTIVE RELAY Page 51 of 53 ...
Страница 189: ...LINE SECTIONALIZING USING A PLC AND ABB PROTECTIVE RELAY Page 52 of 53 ...