ABB REL 356 Current Differential Protection
5-9
Testing
IA
IAR
IB
IBR
IC
ICR
TB6-6
TB6-5
TB6-8
TB6-7
TB6-10
TB6-9
3
∅
Current Test Set
TB6-6
TB6-5
TB6-8
TB6-7
TB6-10
TB6-9
IA
IAR
IB
IBR
IC
ICR
IA
IB
IC
IR
External Fault(s) - Current connections
Unit #1 REL356
Unit #2 REL356
STEP 2
Apply fault currents greater than those shown in Tables 5-1, 5-2 & 5-3 and verify that the relay does not trip on external
faults.
Dual Unit Back to Back Test - Internal Faults
To simulate an internal fault, reverse the CT polarity on unit number 2. Test the relay per Tables 5-1, 5-2 & 5-3 by
applying faults and verifying that the relay trips.
Internal Fault(s) - Current connections
IA
IAR
IB
IBR
IC
ICR
TB6-6
TB6-5
TB6-8
TB6-7
TB6-10
TB6-9
3
Æ
Current Test Set
TB6-6
TB6-5
TB6-8
TB6-7
TB6-10
TB6-9
IA
IAR
IB
IBR
IC
ICR
IA
IB
IC
IR
Содержание REL 356
Страница 23: ...ABB REL 356 Current Differential Protection 1 10 Product Overview and Specifications ...
Страница 83: ...ABB REL 356 Current Differential Protection 3 36 Settings and Application ...
Страница 127: ...ABB REL 356 Current Differential Protection 5 28 Testing ...
Страница 186: ...LINE SECTIONALIZING USING A PLC AND ABB PROTECTIVE RELAY Page 49 of 53 ...
Страница 187: ...LINE SECTIONALIZING USING A PLC AND ABB PROTECTIVE RELAY Page 50 of 53 ...
Страница 188: ...LINE SECTIONALIZING USING A PLC AND ABB PROTECTIVE RELAY Page 51 of 53 ...
Страница 189: ...LINE SECTIONALIZING USING A PLC AND ABB PROTECTIVE RELAY Page 52 of 53 ...