ABB REL 356 Current Differential Protection
5-5
Testing
Functional Tests - Current Differential System
The following section documents all the various types of test that can be done to verify operating characteristics of the
REL 356 relay. If a simple single unit test needs to be performed, the “Singe Unit Loopback Test” will be adequeate for
verification purposes. “Dual Units Back to Back Test” are included for lab type back to back verification tests and are
not necessary for field installation type testing.
Single Unit Loopback Test - Internal Faults
STEP 1
Enter the following settings:
*NOTE* Set the LDT time to 10.8 msec. for 9600 bps communication channel option A, to 19.3 ms for 9600 bps
communication channel option T or 1.3 msec. for 56/64 kbs communication channel.
Modem version A or T is shown in the style number.
STEP 2
Power down the unit.
STEP 3
Make the connections on the reat of the REL 356 that correspond to the type of communication channel that you have
as specified in “Communication Subsystem Test” above.
Freq
=
60
Z2GR
=
2.0
RP
=
NO
CTYP
=
5
CTR
=
5000
VTR
=
7000
OSC
=
TRIP
FDAT
=
TRIP
TRGG
=
0.5
TRGP
=
0.5
CD
=
DI
ILTS
=
OUT
RBEN
=
NORD
OPBR
=
52b
IE
=
0.50
IPL
=
0.50
IPH
=
OUT
IGL
=
0.50
IGH
=
OUT
TDES
=
5.0
OTH
=
0.50
C0
=
0.0
C1
=
0.10
C2
=
0.70
LDFL
=
LEAD
LDT
=
*note*
UNID
=
0
KBPS
=
64
TTRP
=
OUT
XCLK
=
INT
LPBK
=
YES
XMTR
=
XPUD
=
1.500
DTYP
=
KM
PANG
=
75
GANG
=
75
ZR
=
3.0
BKUP
=
OUT
LOPB
=
NO
FDOP
=
IN
FDOG
=
IN
DIRU
=
ZSEQ
IOM
=
0.5
TOG
=
BLK
Z2P
=
4.0
T2P
=
0.1
Z2GF
=
4.0
ALDT
=
NO
Z2GF
=
4.0
Z2GR
=
2.0
T2G
=
0.1
Z3P
=
7.0
T3P
=
1.0
Z3GF
=
7.0
Z3GR
=
3.5
T3G
=
1.0
OST
=
WAYO
OSB
=
BOTH
RT
=
2.0
RU
=
4.0
OST1
=
2
OST2
=
3
OST3
=
3
OSOT
=
100
SETR
=
YES
TIME
=
CURRENT
YEAR
=
CURRENT
MNTH
=
CURRENT
DAY
=
CURRENT
HOUR
=
CURRENT
MIN
=
CURRENT
SOBT
=
16
DDTT
=
0
RLSD
=
Содержание REL 356
Страница 23: ...ABB REL 356 Current Differential Protection 1 10 Product Overview and Specifications ...
Страница 83: ...ABB REL 356 Current Differential Protection 3 36 Settings and Application ...
Страница 127: ...ABB REL 356 Current Differential Protection 5 28 Testing ...
Страница 186: ...LINE SECTIONALIZING USING A PLC AND ABB PROTECTIVE RELAY Page 49 of 53 ...
Страница 187: ...LINE SECTIONALIZING USING A PLC AND ABB PROTECTIVE RELAY Page 50 of 53 ...
Страница 188: ...LINE SECTIONALIZING USING A PLC AND ABB PROTECTIVE RELAY Page 51 of 53 ...
Страница 189: ...LINE SECTIONALIZING USING A PLC AND ABB PROTECTIVE RELAY Page 52 of 53 ...