Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M0201
20 Chapter 3
Table 3.4
Type
PSE 18
PSE 25
PSE 30
PSE 37
Rated Current Ie (A)
18
25
30
37
Motor size 380 - 415 V (
kW)
7.5
11
15
18.5
Motor size 480 V (
hp)
10
15
20
25
Motor size 600 V (hp)
15
20
25
30
Power loss at Rated Current (W)
0.2
0.4
0.5
0.8
Power supply requirements holding
(VA)
16
16
16
16
Power supply requirements pull-in
value (VA)
19,9
19,9
19,9
19,9
Table 3.5
Type
PSE 45
PSE 60
PSE 72
PSE 85
Rated Current Ie (A)
45
60
72
85
Motor size 380 - 415 V (kW)
22
30
37
45
Motor size 480 V (hp)
30
40
50
60
Motor size 600 V (hp)
40
50
60
75
Power loss at Rated Current (W)
1.2
2.2
3.1
4.3
Power supply requirements holding
(VA)
16
16
16
16
Power supply requirements pull-in
value (VA)
19,9
19,9
19,9
19,9
Table 3.6
Type
PSE 105 PSE 142 PSE 170 PSE 210
Rated Current Ie (A)
106
143
171
210
Motor size 380 - 415 V (kW)
55
75
90
110
Motor size 480 V (hp)
75
100
125
150
Motor size 600 V (hp)
100
125
150
200
Power loss at Rated Current (W)
6.6
12.1
17.6
8.8
Power supply requirements holding
(VA)
16
16
16
23
Power supply requirements pull-in
value (VA)
19,9
31
31
350
3.7.3 PSE Softstarter types
Table 3.7
Type
PSE 250 PSE 300 PSE 370
Rated Current Ie (A)
250
302
370
Motor size 380 - 415 V (kW)
132
160
200
Motor size 480 V (hp)
200
250
300
Motor size 600 V (hp)
250
300
350
Power loss at Rated Current (W)
12.5
18
27.4
Power supply requirements holding
(VA)
23
23
23
Power supply requirements pull-in
value (VA)
350
350
350