Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M0201
51
Chapter 6
Information Level
A
%
Cos
j
V
Lock/Unlock Settings Level
Reset all parameter settings to user default values
PSE
Ie (Rated current of motor)
Individual
Settings level
Start Ramp time
OFF, 1...30 s
Stop Ramp time
OFF, 1...30 s
Initial/End Voltage
30...70 %
Current Limit
1.5...7 x Ie
Torque Control during start ramp
OFF
On
Setting of time must be performed in Start Ramp
time
OFF
Torque Control during stop ramp
On
Setting of time must be performed in Stop Ramp
time
OFF
Operational time
Normal ramp
Ramp with Kick Start
t
Ue
Set Initial Voltage
Kick Start
30...100
OFF
Operational time
Normal ramp
Ramp with Kick Start
t
Ue
Set Initial Voltage
Electronic Motor Overload Protection
HAnd
10A/10/20/30
Auto
OFF
Underload Protection
HAnd
0.2...1 x Ie
Auto
OFF
Locked Rotor Protection
Hand
0.5...7 x Ie
Auto
OFF
0...255 (readable)
dPoF
dPon
FieldBus Control
dPoF
HAnd
On
0...255
trIP
dPon
Auto
LocC
Figure 6.8: Menu structure PSE Softstarter
Exit
Select
Reset
1SFC132291F0001