Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M0201
57
Chapter 7
7.3 List of
available parameters
A list of the available parameters for PSE18...PSE370 is visible in table 7.1.
Table 7.1
Description
Display
symbol
Setting range
Default
value
Access
from
Parameter
transfer with
Exter
nal
Keypad
Actual setting
HMI
Fieldbus
Rated Current of motor Ie
Individual
See tables in
chapter 3.7.3
PSE Softstarter
types. Setting
range is 30-100
percent of Ie
Individual
W
W
Start Ramp time
1...30 s
10 s
W
W
T
Stop Ramp time
OFF, 1...30 s
OFF
W
W
T
Initial/End Voltage
30...70 %
30 %
W
W
T
Current limit
1.5 x 7 Ie
4.0 x Ie
W
W
T
Torque Control during start ramp
OFF/On
OFF
W
W
T
Torque Control during stop ramp
OFF/On
On
W
W
T
Kick Start
OFF, 30...70 %
OFF
W
W
T
Electronic Motor Overload Protection
(EOL)
T
Tripping Class (EOL)
10 A, 10, 20,
30
10
W
W
T
Type of operation (EOL)
HAnd/Auto
1
HAnd
X
X
T
R = Readable
W = Writeable
T = Will be transferred (uploaded/downloaded)