Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M0201
22 Chapter 3
3.7.5
information
Examples of equipment suitable for use in a circuit with maximum available fault
current as shown when protected by devices indicated. See table 3.9. For more
information see: http://www.abbcontrol.fr/coordination_tables/coordtable.htm
Table 3.9
Softstarter
Type
Fuses
MCCB
MCCB
Normal breaker
Standard breaker
550-600V
440-480V
550-600V
440-480V
550-600V
High Fault
Current
85kA
Class J
Fuses
High Fault
Current
High Fault
Current
Normal breaker
High
Fault
Current
High
Fault
Current
Standard
breaker
PSE18-600-70
40A
25kA
14kA
Ts3N070TW
35kA
25kA
Ts3L070TW
PSE25-600-70
50A
Ts3N100TW
Ts3L100TW
PSE30-600-70
60A
Ts3N100TW
Ts3L100TW
PSE37-600-70
80A
Ts3N125TW
Ts3L125TW
PSE45-600-70
100A
Ts3N150TW
Ts3L150TW
PSE60-600-70
125A
Ts3N150TW
Ts3L150TW
PSE72-600-70
150A
18kA
T4N250TW
T4S250TW
PSE85-600-70
175A
T5N300TW
T5S300TW
PSE105-600-70
225A
T5N300TW
T5S300BW
PSE142-600-70
300A
T5N400BW
T5S400BW
PSE170-600-70
350A
T5N400BW
T5S400BW
PSE210-600-70
450A
35kA
20kA
T6N600BW
50kA
T6S600BW
PSE250-600-70
500A
T6N600BW
T6S800BW
PSE300-600-70
600A
T6N800BW
T6S800BW
PSE370-600-70
600A
T6N800BW
T6S800BW