Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M0201
74 Chapter 7
7.7 Special functions
7.7.1 Reset all parameter
settings to user
default values
Start from Information Level and press in sequence the keys Exit and Select for a
few seconds, as described in figure 7.29. The text string “rES” will be displayed
on the
LCD as in figure 7.34.
Press Select to enter Reset
All Settings, and the text string “rES” on the LCD
starts flashing.
Press Exit key to cancel, or press Select to reset all settings.
After reset it is necessary to press Exit for returning to Information Level.
Caution
!
The motor may start unexpectedly if there is a start signal present when do
-
ing any of the actions listed below.
•
Switching from one type of control to another (fieldbus control /
hard-
wire control)
•
Resetting all parameters
•
Resetting
events
•
If using automatic event reset
Figure 7.34: Reset All Settings to user default
values parameter displayed
Figure 7.33: Entering menu Reset all settings
to user default values
Ready
Run
Exit
Select
Reset
Protection
Fault