Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M0201
77
Chapter 7
7.9 Application
settings
In table 7.4 the recommended parameter settings for different applications are
described.
Table 7.4: Application settings
Recommended basic setting
Centrifugal
fan
10 s
OFF
40 %
5.0 x Ie
OFF
OFF
Axial fan
10 s
OFF
40 %
5.0 x Ie
OFF
OFF
Centrifugal
pump
10 s
10 s
40 %
5.0 x Ie
OFF
On
High pressure
pump
10 s
10 s
50 %
5.5 x Ie
OFF
On
Compressor
5 s
OFF
40 %
4.5 x Ie
OFF
OFF
Grinder
10 s
OFF
40 %
5.0 x Ie
OFF
OFF
Mixer
10 s
OFF
40 %
5.0 x Ie
OFF
OFF
Bow thruster
10 s
OFF
40 %
4.5 x Ie
OFF
OFF
Hydraulic pump
10 s
OFF
40 %
4.5 x Ie
OFF
OFF
Crusher
10 s
OFF
40 %
5.0 x Ie
OFF
OFF
Conveyor belt
10 s
OFF
50 %
5.0 x Ie
OFF
OFF
Escalator
10 s
OFF
40 %
4.5 x Ie
OFF
OFF
Lift/Elevator
10 s
OFF
40 %
4.5 x Ie
OFF
OFF
Cutter
10 s
OFF
40 %
5.0 x Ie
OFF
OFF
Band saw
10 s
OFF
40 %
5.0 x Ie
OFF
OFF
Circular saw
10 s
OFF
40 %
5.0 x Ie
OFF
OFF
Please note that the parameter values above are to be used as a guide only. Variations in load
conditions may require additional tuning.
For Heavy Duty applications the Initial/End Voltage
as well as the Current Limit
might need to be increased.