Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M0201
75
Chapter 7
7.7.2 PSE parameter
This parameter contains information about the type of PSE Softstarter which is
available. The PSE parameter must be configured after replacing the PCB. This
parameter must not be changed if the PCB has not been replaced. Read chap-
ter 3.3 Type designation to get information about how to find out the size of the
softstarter.
Start from Information Level and press in sequence the keys Exit, Select and Ar-
row Up for a few seconds, see figure 7.31. The text string “Id” will be displayed on
the
LCD as in figure 7.36.
Press Select to enter parameter PSE, and the text string “Id” the LCD starts flash
-
ing.
Press Exit to return to Information level or Scroll to configure according to the
softstarters size. Press Select to confirm.
Configure parameter PSE only if the printed circuit board has been replaced.
Figure 7.35: Entering PSE parameter
Ready
Run
Exit
Select
Reset
Protection
Fault
Figure 7.36: PSE parameter displayed