Softstarters Type PSE18...PSE370 Installation and commissioning manual 1SFC132057M0201
58 Chapter 7
R = Readable
W = Writeable
HAnd = Manual reset of the protection or fault.
Auto = Automatic reset of the protection or fault.
OFF = Fieldbus is not allowed to control the motor.
On = Fieldbus is allowed to control the motor.
255 = Address of the FieldBusPlug will be used.
dPon = Download of parameters from PLC enabled.
dPoF = Download of parameters from PLC blocked.
Accessible only if On is previously selected.
trIP = Trip on fault.
LocC = Local control on fault - hardwire control is possible
Accessible only if trIP is previously selected.
HAnd = Manual reset of the protection or fault.
Auto = Automatic reset of the protection or fault.
1
2
4
5
6
3
Underload Protection
T
Level
OFF
W
W
T
Type of operation
1
HAnd
W
W
T
Locked Rotor
Protection
T
Level
OFF
W
W
T
Type of operation
1
HAnd
W
W
T
Fieldbus Control
1SFC13235F0001
OFF/On
2
OFF
W
R
T
Fieldbus address
255
255
3
W
R
T
Download Parameter
dPoF/dPon
4
dPon
W
R
T
Fieldbus Operation When Fault
LocC/trIP
5
LocC
W
R
T
Type of Operation
HAnd/Auto
6
HAnd
W
R
T
Description
Display
symbol
Setting range
Default
value
Access
from
Parameter
transfer with
Exter
nal
Keypad
Actual setting
HMI
Fieldbus
T = Will be transferred (uploaded/downloaded)