1.1 Technical data
Standards
Type-tested switchgear assemblies (TTA)*
Low-voltage switchgear and control gear assem-
blies **
Power switchgear and control gear assemblies **
IEC 60439-1,
IEC 61439 -1 and -2
EN 61439-1 and -2
Test certificates
Germanischer Lloyd, Hamburg / Germany
ASTA, UK
IPH, Institut für Prüffeld- und Hochspannungstechnik, Berlin / Germany
DLR German Research Institute for Aerospace e. V., Jülich / Germany
IABG Industrieanlagen Betriebsgesellschaft, München / Germany
Electrical
data
Rated voltages
Rated insulation voltage Ui
Rated operating voltage Ue
Rated impulse withstand voltage Uimp
Overvoltage category
Degree of pollution
Rated frequency
1000 V 3~, 1500 V- **
690 V 3~, 750 V-
6 / 8 / 12 kV, depending on equipment
II / III / IV
3
up to 60 Hz
Rated currents
Busbars:
Rated current Ie
Rated peak withstand current Ipk
Rated short-time withstand current Icw
Distribution bars:
Rated current I
e
Rated peak withstand current Ipk
Rated short-time withstand current Icw
up to 6300 A
up to 250 kA
up to 100 kA
up to 2000 A
up to 176 kA
up to 80 kA
Mechanical
character-
istics
Dimensions
Cubicles and frames
Recommended height
Recommended width
Recommended depth
Basic grid size
DIN 41488
2200
mm
400,
600
, 800,
1000
, 1200 mm
400,
600
, 800, 1000, 1200 mm
E = 25 mm acc. to DIN 43660
Surface protection
Frame
Internal subdivision
Enclosure
Zinc or Alu-zinc coated
Zinc or Alu-zinc coated
Zinc or Alu-zinc coated and
Powder coated RAL 7035, light grey
Degrees of
protection
According to IEC 60529
IP 30 up to IP 54
Plastic components
Halogen-free, self-extinguishing,
flame retardant, CFC-free
IEC 60707, DIN VDE 0304 part 3
Internal
subdivision
Device compartment - device compartment
Busbar compartment - cable compartment
Busbar compartment - device compartment
Device compartment - cable compartment
Form 4
Extras
Paint finish
Enclosure
Special colours (standard RAL 7035)
Busbar system
Busbars
Insulated
Silver or tin galvanized
*
Definition TTA: Switchgear assembly corresponding, to a large degree, with the original type or system of switchgear assembly type-tested
in accordance with these standards.
**
Design verification by testing: When an assembly has previously been tested in accordance with IEC 60439-1 , and the results fulfil the
requirements of IEC61439 -1 / -2, the verification of these requirements need not to be repeated
***
Depending on the electrical equipment.