FCA/S 1.x.x.1 | 2CDC508134D0202   95 

Operation mode output C and D 

Options: 

Individual 

 

Valve drive, motor-driven (3-point) 

 

 

 

This parameter determines whether the operation modes of outputs C and D can be parameterized 
individually or whether the outputs are operated in operation mode 

Valve drive, motor-driven (3-point)

The outputs are linked to one another in pairs in this operation mode. Outputs C and D control the 
contacts Open/Close of the valve drive for opening/closing the valve. 

 

Individual:

 With this setting, the operation modes of outputs C and D are set individually from one 

another. 

Dependent parameters: 

Output C 

Output D 

Options: 

Disabled 

 

Valve drive, thermoelectric (PWM) 

 

 

This parameter defines the individual operation mode of the output. 

 

Disabled:

 No operation mode selected. 

 

Valve drive, thermoelectric (PWM):

 The parameter (window) and communication objects for the 

operation mode 

Valve drive, thermoelectric (PWM)

 are enabled. 

 

Valve drive, motor-driven (3-point):

 The parameter (window) and communication objects for the 

operation mode 

Valve drive, motor-driven (3-point)

 are enabled. 

Output C 

Open 

Output D 

Close 

 

Assignment of the valves 

Note 

Outputs A and C are automatically assigned via the selection in the parameter 

Fan Coil operating mode

 

Содержание i-bus KNX

Страница 1: ...ABB i bus KNX Fan Coil Actuators FCA S Product Manual ...

Страница 2: ......

Страница 3: ...d tolerances 26 2 2 6 Resistance signals 26 2 2 7 Fan rated current 6 A 28 2 2 8 Fan lamp load 6 A 29 2 2 9 Output rated current 20 AX 30 2 2 10 Output lamp load 20 AX 31 2 2 11 Connection diagram thermoelectric PWM 32 2 2 12 Dimension drawing 34 2 3 Fan Coil Actuator FCA S 1 2 1 2 0 10V MDRC 35 2 3 1 Technical data 35 2 3 2 Outputs valve V1 2 analog 37 2 3 3 Inputs 37 2 3 4 Resolution accuracy an...

Страница 4: ...3 18 Parameter window Automatic control One level 156 3 2 3 19 Parameter window E F G Output switch actuators 162 3 2 3 20 Parameter window H Output 163 3 2 3 20 1 Parameter window Time 166 3 2 4 Parameter window Inputs a c 170 3 2 4 1 Parameter window Enable inputs a c 170 3 2 4 2 Parameter window a Switch sensor 171 3 2 4 2 1 Parameter Distinction between long and short operation No 173 3 2 4 2 ...

Страница 5: ...nction 246 4 2 2 1 Staircase light 246 4 3 Valve drives valves and controller 247 4 3 1 Electromotor Valve Drives 247 4 3 2 Electrothermal Valve Drives 247 4 3 3 Control types 248 4 3 3 1 Continuous control 248 4 3 3 2 Pulse width modulation PWM 249 4 3 3 3 Pulse width modulation calculation 251 4 4 Reaction on bus voltage failure recovery download and ETS reset 252 4 4 1 Bus voltage recovery 252 ...

Страница 6: ......

Страница 7: ...additional contact is possible for example for control of an electric heater Fan Coil Actuators vary in the way they control the valves The Fan Coil Actuators FCA S 1 1 x 2 have two outputs for control of motor power operated or thermal heating and cooling valves The Fan Coil Actuators FCA S 1 2 x 2 have two outputs for control of analog heating and cooling valves 1 1 Using the product manual This...

Страница 8: ...mportant These safety instructions are used as soon as there is danger of a malfunction without risk of damage or injury Attention These safety instructions are used as soon as there is danger of a malfunction without risk of damage or injury Danger These safety instructions are used if there is a danger to life and limb with inappropriate use Danger These safety instructions are used if there is ...

Страница 9: ...ign with 6 module widths for installation in a distribution board Connection to the ABB i bus KNX is via the front bus connection terminal The devices require no auxiliary voltage The assignment of the physical address as well as the setting of parameters is carried out with Engineering Tool Software ETS Product name description Abbreviatio n Description F Fan C Coil A Actuator S MDRC x 1 Single x...

Страница 10: ...perature sensor e g exhaust temperature 1 1 1 1 Outputs 6 A switch 3 3 3 3 3 speed fan or 1 1 1 1 2 speed fan or 1 1 1 1 1 speed fan or 1 1 1 1 3 individual outputs 3 3 3 3 Outputs 16 A 10 AX switch 1 1 Electrical auxiliary heater 1 1 Outputs 20 AX switch 1 1 Electrical auxiliary heater 1 1 Outputs electronic 0 5 A 4 4 Thermoelectric Valve Drives PWM 4 4 Motor Driven Valve Drives 3 point 2 2 Outpu...

Страница 11: ...he i bus Tool The output values are still sent to the bus if cyclical sending is selected The i bus tool can be used to define temperature values via the communication object so that the KNX system can be tested during commissioning without the need to connect a temperature sensor The i bus Tool can be downloaded for free from our website www abb com knx ETS is not required for the Software Tool H...

Страница 12: ......

Страница 13: ...oltage 2 1 1 Technical data Supply Bus voltage 21 32 V DC Current consumption bus 12 mA Leakage loss bus Maximum 250 mW Leakage loss device Maximum 3 05 W The maximum power consumption of the device results from the following specifications KNX connection Relay 16 A Relay 6 A Electronic outputs 0 25 W 1 0 W 0 6 W 1 2 W Connections KNX Via bus connection terminal Inputs Outputs Via screw terminals ...

Страница 14: ...xtra low voltage SELV 24 V DC Temperature range Operation Transport Storage 5 C 45 C 25 70 C 25 55 C Temperatures exceeding 45 C reduce the service life Ambient conditions Maximum air humidity 93 no condensation allowed Design Modular installation device MDRC Modular installation device ProM Dimensions 108 x 90 x 64 5 mm H x W x D Mounting width in space units 6x 18 mm modules Mounting depth 64 5 ...

Страница 15: ...s thermoelectric PWM Rated values Quantity 4 non isolated short circuit proofed Un rated voltage 24 230 V AC 50 60 Hz In rated current per output pair 0 5 A Continuous current 0 5 A resistive load at Tu up to 20 C 0 3 A resistive load at Tu up to 60 C Starting current Maximum 1 6 A 10 s at Tu up to 60 C Tu ambient temperature Minimum load 0 5 VA per PWM output 2 1 3 Valve outputs motor driven 3 po...

Страница 16: ...of the device is not affected After calibration has been completed the calibration values which have been determined will be stored in the non volatile memory Thereafter the device will achieve this level of accuracy every time it is switched on If the calibration is interrupted by programming or bus voltage failure it will recommence every time it is restarted The ongoing calibration is displayed...

Страница 17: ...is sensor is preferred KT KTY The KT KTY has a low level of accuracy can only be exchanged under certain circumstances and can only be used for very simple applications Please note that there are different tolerance classes for the sensors in the versions PT100 and PT1000 The table indicates the individual classes according to IEC 60 751 date 2008 Description Tolerance Class AA 0 10 C 0 0017 x t C...

Страница 18: ...al delay of the relay is approx 20 ms What do the terms AC1 AC3 and AC5a mean In intelligent installation systems different switching capacities and performance specifications that are dependent on the special applications have become established in domestic and industrial installations These performance specifications are rooted in the respective national and international standards The tests are...

Страница 19: ... 800 W 800 W Mercury vapor lamp Uncompensated Parallel compensated 1 000 W 800 W Switching capacity switching contact Maximum peak inrush current Ip 150 s 200 A Maximum peak inrush current Ip 250 s 160 A Maximum peak inrush current Ip 600 s 100 A Number of electronic ballasts T5 T8 single element 1 18 W ABB EVG 1 x 18 SF 10 24 W ABB EVG T5 1 x 24 CY 10 36 W ABB EVG 1 x 36 CF 7 58 W ABB EVG 1 x 58 ...

Страница 20: ...at do the terms AC1 AC3 and AC5a mean In intelligent installation systems different switching capacities and performance specifications that are dependent on the special applications have become established in domestic and industrial installations These performance specifications are rooted in the respective national and international standards The tests are defined to simulate typical application...

Страница 21: ...ed 1 100 W 1 100 W Mercury vapor lamp Uncompensated Parallel compensated 2 000 W 2 000 W Switching capacity switching contact Maximum peak inrush current Ip 150 s 400 A Maximum peak inrush current Ip 250 s 320 A Maximum peak inrush current Ip 600 s 200 A Number of electronic ballasts T5 T8 single element 1 18 W ABB EVG 1 x 18 SF 23 24 W ABB EVG T5 1 x 24 CY 23 36 W ABB EVG 1 x 36 CF 14 58 W ABB EV...

Страница 22: ...FCA S 1 x x 1 2 1 11 Connection diagram motor driven 3 point FCA S 1 1 1 2 1 Label carrier 6 Valve V1 e g heating 2 Programming button 7 Valve V2 e g cooling 3 Programming LED red 8 Fan 4 Bus connection terminal 9 Output H 5 Inputs a b c 2CDC072014F0015 ...

Страница 23: ...trol value 1 valve free free free 2 control values 1 valve free free free 2 control values 2 valves free free Setting facilities for valve drives Thermoelectric PWM Separate heating cooling Direction OPEN CLOSE OPEN CLOSE OPEN CLOSE OPEN CLOSE Motor driven 3 point Separate heating cooling Direction OPEN CLOSE OPEN CLOSE Function is supported Function is not supported free Is available and can be u...

Страница 24: ...ABB i bus KNX Device technology 22 2CDC508134D0202 FCA S 1 x x 1 2 1 12 Dimension drawing 2CDC072016F0013 ...

Страница 25: ... 1 Technical data Supply Bus voltage 21 32 V DC Current consumption bus 12 mA Leakage loss bus Maximum 250 mW Leakage loss device Maximum 3 05 W The maximum power consumption of the device results from the following specifications KNX connection Relay 16 A Relay 6 A Electronic outputs 0 25 W 1 0 W 0 6 W 1 2 W Connections KNX Via bus connection terminal Inputs Outputs Via screw terminals Connection...

Страница 26: ... To DIN EN 60 529 Protection class II To DIN EN 61 140 Isolation category Overvoltage category III according to DIN EN 60 664 1 Pollution degree II to DIN EN 60 664 1 KNX safety extra low voltage SELV 24 V DC Temperature range Operation Transport Storage 5 C 45 C 25 70 C 25 55 C Temperatures exceeding 45 C reduce the service life Ambient conditions Maximum air humidity 93 no condensation allowed D...

Страница 27: ...rmoelectric PWM Rated values Quantity 4 non isolated short circuit proofed Un rated voltage 24 230 V AC 50 60 Hz In rated current per output pair 0 5 A Continuous current 0 5 A resistive load at Tu up to 20 C 0 3 A resistive load at Tu up to 60 C Starting current Maximum 1 6 A 10 s at Tu up to 60 C Tu ambient temperature Minimum load 0 5 VA per PWM output 2 2 3 Valve outputs motor driven 3 point R...

Страница 28: ...ffected After calibration has been completed the calibration values which have been determined will be stored in the non volatile memory Thereafter the device will achieve this level of accuracy every time it is switched on If the calibration is interrupted by programming or bus voltage failure it will recommence every time it is restarted The ongoing calibration is displayed in the status byte by...

Страница 29: ...is sensor is preferred KT KTY The KT KTY has a low level of accuracy can only be exchanged under certain circumstances and can only be used for very simple applications Please note that there are different tolerance classes for the sensors in the versions PT100 and PT1000 The table indicates the individual classes according to IEC 60 751 date 2008 Description Tolerance Class AA 0 10 C 0 0017 x t C...

Страница 30: ...al delay of the relay is approx 20 ms What do the terms AC1 AC3 and AC5a mean In intelligent installation systems different switching capacities and performance specifications that are dependent on the special applications have become established in domestic and industrial installations These performance specifications are rooted in the respective national and international standards The tests are...

Страница 31: ... 800 W 800 W Mercury vapor lamp Uncompensated Parallel compensated 1 000 W 800 W Switching capacity switching contact Maximum peak inrush current Ip 150 s 200 A Maximum peak inrush current Ip 250 s 160 A Maximum peak inrush current Ip 600 s 100 A Number of electronic ballasts T5 T8 single element 1 18 W ABB EVG 1 x 18 SF 10 24 W ABB EVG T5 1 x 24 CY 10 36 W ABB EVG 1 x 36 CF 7 58 W ABB EVG 1 x 58 ...

Страница 32: ...the relay is approx 20 ms What do the terms AC1 AC3 and AC5a mean In intelligent installation systems different switching capacities and performance specifications that are dependent on the special applications have become established in domestic and industrial installations These performance specifications are rooted in the respective national and international standards The tests are defined to ...

Страница 33: ...r lamp Uncompensated Parallel compensated 3 680 W 3 680 W Switching capacity switching contact Maximum peak inrush current Ip 150 s 600 A Maximum peak inrush current Ip 250 s 480 A Maximum peak inrush current Ip 600 s 300 A Number of electronic ballasts T5 T8 single element 1 18 W ABB EVG 1 x 18 SF 262 24 W ABB EVG T5 1 x 24 CY 262 36 W ABB EVG 1 x 36 CF 22 58 W ABB EVG 1 x 58 CF 122 80 W Helvar E...

Страница 34: ...button LED yellow 3 Programming LED red 11 Valve output A B buttons LEDs e g heating yellow 4 Bus connection terminal 12 Valve output C D buttons LEDs e g cooling yellow 5 Inputs a b c 13 Output E F G button LEDs fan speed 1 2 3 yellow 6 Valve output A B e g heating 14 Output H button 7 Valve output C D e g cooling 15 Inputs a b c buttons LEDs yellow 8 Fan 16 Output H display 2CDC072015F0015 ...

Страница 35: ...trol value 1 valve free free free 2 control values 1 valve free free free 2 control values 2 valves free free Setting facilities for valve drives Thermoelectric PWM Separate heating cooling Direction OPEN CLOSE OPEN CLOSE OPEN CLOSE OPEN CLOSE Motor driven 3 point Separate heating cooling Direction OPEN CLOSE OPEN CLOSE Function is supported Function is not supported free Is available and can be u...

Страница 36: ...ABB i bus KNX Device technology 34 2CDC508134D0202 FCA S 1 x x 1 2 2 12 Dimension drawing 2CDC072031F0011 ...

Страница 37: ... 2 3 1 Technical data Supply Bus voltage 21 32 V DC Current consumption bus 12 mA Leakage loss bus Maximum 250 mW Leakage loss device Maximum 2 W The maximum power consumption of the device results from the following specifications KNX connection Relay 16 A Relay 6 A Analog outputs 0 25 W 1 0 W 0 6 W 0 15 W Connections KNX Via bus connection terminal Inputs Outputs Via screw terminals Connection t...

Страница 38: ...xtra low voltage SELV 24 V DC Temperature range Operation Transport Storage 5 C 45 C 25 70 C 25 55 C Temperatures exceeding 45 C reduce the service life Ambient conditions Maximum air humidity 93 no condensation allowed Design Modular installation device MDRC Modular installation device ProM Dimensions 108 x 90 x 64 5 mm H x W x D Mounting width in space units 6x 18 mm modules Mounting depth 64 5 ...

Страница 39: ...ntilation Air Conditioning Fan Coil Actuator 0 10V The device does not support the locking function of a KNX device in ETS If you use a BCU code to inhibit access to all the project devices this has no effect on this device Data can still be read and programmed 2 3 2 Outputs valve V1 2 analog Rated values Quantity 2 non isolated short circuit proofed Control signal 0 10 V DC Signal type Analog Out...

Страница 40: ... of the device is not affected After calibration has been completed the calibration values which have been determined will be stored in the non volatile memory Thereafter the device will achieve this level of accuracy every time it is switched on If the calibration is interrupted by programming or bus voltage failure it will recommence every time it is restarted The ongoing calibration is displaye...

Страница 41: ...is sensor is preferred KT KTY The KT KTY has a low level of accuracy can only be exchanged under certain circumstances and can only be used for very simple applications Please note that there are different tolerance classes for the sensors in the versions PT100 and PT1000 The table indicates the individual classes according to IEC 60 751 date 2008 Description Tolerance Class AA 0 10 C 0 0017 x t C...

Страница 42: ...al delay of the relay is approx 20 ms What do the terms AC1 AC3 and AC5a mean In intelligent installation systems different switching capacities and performance specifications that are dependent on the special applications have become established in domestic and industrial installations These performance specifications are rooted in the respective national and international standards The tests are...

Страница 43: ... 800 W 800 W Mercury vapor lamp Uncompensated Parallel compensated 1 000 W 800 W Switching capacity switching contact Maximum peak inrush current Ip 150 s 200 A Maximum peak inrush current Ip 250 s 160 A Maximum peak inrush current Ip 600 s 100 A Number of electronic ballasts T5 T8 single element 1 18 W ABB EVG 1 x 18 SF 10 24 W ABB EVG T5 1 x 24 CY 10 36 W ABB EVG 1 x 36 CF 7 58 W ABB EVG 1 x 58 ...

Страница 44: ...What do the terms AC1 AC3 and AC5a mean In intelligent installation systems different switching capacities and performance specifications that are dependent on the special applications have become established in domestic and industrial installations These performance specifications are rooted in the respective national and international standards The tests are defined to simulate typical applicati...

Страница 45: ...ed 1 100 W 1 100 W Mercury vapor lamp Uncompensated Parallel compensated 2 000 W 2 000 W Switching capacity switching contact Maximum peak inrush current Ip 150 s 400 A Maximum peak inrush current Ip 250 s 320 A Maximum peak inrush current Ip 600 s 200 A Number of electronic ballasts T5 T8 single element 1 18 W ABB EVG 1 x 18 SF 23 24 W ABB EVG T5 1 x 24 CY 23 36 W ABB EVG 1 x 36 CF 14 58 W ABB EV...

Страница 46: ...nection diagram FCA S 1 2 1 2 1 Label carrier 6 Valve V1 e g heating 2 Programming button 7 Valve V2 e g cooling 3 Programming LED red 8 Fan 4 Bus connection terminal 9 Output H 5 Inputs a b c Note Terminals 1 and 4 on the FCA S 1 2 1 2 are not used internally 2CDC072018F0013 ...

Страница 47: ... drives allocated to the Fan Coil unit Analog 0 10 V 1 control value 1 valve free 2 control values 1 valve free 2 control values 2 valves Setting facilities for valve drives Analog 0 10 V Separate heating cooling Direction OPEN CLOSE OPEN CLOSE Function is supported Function is not supported free Is available and can be used separately Functions of the output I E G H Switch function Normally close...

Страница 48: ...ABB i bus KNX Device technology 46 2CDC508134D0202 FCA S 1 x x 1 2 3 11 Dimension drawing 2CDC072015F0013 ...

Страница 49: ... 2 4 1 Technical data Supply Bus voltage 21 32 V DC Current consumption bus 12 mA Leakage loss bus Maximum 250 mW Leakage loss device Maximum 2 W The maximum power consumption of the device results from the following specifications KNX connection Relay 16 A Relay 6 A Analog outputs 0 25 W 1 0 W 0 6 W 0 15 W Connections KNX Via bus connection terminal Inputs Outputs Via screw terminals Connection t...

Страница 50: ...DIN EN 60 529 Protection class II To DIN EN 61 140 Isolation category Overvoltage category III according to DIN EN 60 664 1 Pollution degree II to DIN EN 60 664 1 KNX safety extra low voltage SELV 24 V DC Temperature range Operation Transport Storage 5 C 45 C 25 70 C 25 55 C Temperatures exceeding 45 C reduce the service life Ambient conditions Maximum air humidity 93 no condensation allowed Desig...

Страница 51: ...tion Air Conditioning Fan Coil Actuator 0 10V The device does not support the locking function of a KNX device in ETS If you use a BCU code to inhibit access to all the project devices this has no effect on this device Data can still be read and programmed 2 4 2 Outputs valve V1 2 analog Rated values Quantity 2 non isolated short circuit proofed Control signal 0 10 V DC Signal type Analog Output l...

Страница 52: ...ffected After calibration has been completed the calibration values which have been determined will be stored in the non volatile memory Thereafter the device will achieve this level of accuracy every time it is switched on If the calibration is interrupted by programming or bus voltage failure it will recommence every time it is restarted The ongoing calibration is displayed in the status byte by...

Страница 53: ...is sensor is preferred KT KTY The KT KTY has a low level of accuracy can only be exchanged under certain circumstances and can only be used for very simple applications Please note that there are different tolerance classes for the sensors in the versions PT100 and PT1000 The table indicates the individual classes according to IEC 60 751 date 2008 Description Tolerance Class AA 0 10 C 0 0017 x t C...

Страница 54: ... delay of the relay is approx 20 ms What do the terms AC1 AC3 and AC5a mean In intelligent installation systems different switching capacities and performance specifications that are dependent on the special applications have become established in domestic and industrial installations These performance specifications are rooted in the respective national and international standards The tests are d...

Страница 55: ... 800 W 800 W Mercury vapor lamp Uncompensated Parallel compensated 1 000 W 800 W Switching capacity switching contact Maximum peak inrush current Ip 150 s 200 A Maximum peak inrush current Ip 250 s 160 A Maximum peak inrush current Ip 600 s 100 A Number of electronic ballasts T5 T8 single element 1 18 W ABB EVG 1 x 18 SF 10 24 W ABB EVG T5 1 x 24 CY 10 36 W ABB EVG 1 x 36 CF 7 58 W ABB EVG 1 x 58 ...

Страница 56: ...the relay is approx 20 ms What do the terms AC1 AC3 and AC5a mean In intelligent installation systems different switching capacities and performance specifications that are dependent on the special applications have become established in domestic and industrial installations These performance specifications are rooted in the respective national and international standards The tests are defined to ...

Страница 57: ...r lamp Uncompensated Parallel compensated 3 680 W 3 680 W Switching capacity switching contact Maximum peak inrush current Ip 150 s 600 A Maximum peak inrush current Ip 250 s 480 A Maximum peak inrush current Ip 600 s 300 A Number of electronic ballasts T5 T8 single element 1 18 W ABB EVG 1 x 18 SF 262 24 W ABB EVG T5 1 x 24 CY 262 36 W ABB EVG 1 x 36 CF 22 58 W ABB EVG 1 x 58 CF 122 80 W Helvar E...

Страница 58: ...ED red 11 Valve output A buttons LEDs e g heating yellow 4 Bus connection terminal 12 Valve output C buttons LEDs e g cooling yellow 5 Inputs a b c 13 Button LEDs fan speed 1 2 3 yellow 6 Valve output A e g heating 14 Output H button 7 Valve output C e g cooling 15 Inputs a b c buttons LEDs yellow 8 Fan 16 Output H display Note Terminals 1 and 4 on the FCA S 1 2 2 2 are not used internally 2CDC072...

Страница 59: ... drives allocated to the Fan Coil unit Analog 0 10 V 1 control value 1 valve free 2 control values 1 valve free 2 control values 2 valves Setting facilities for valve drives Analog 0 10 V Separate heating cooling Direction OPEN CLOSE OPEN CLOSE Function is supported Function is not supported free Is available and can be used separately Functions of the output I E G H Switch function Normally close...

Страница 60: ...ABB i bus KNX Device technology 58 2CDC508134D0202 FCA S 1 x x 1 2 4 11 Dimension drawing 2CDC072015F0012 ...

Страница 61: ...t be exceeded During planning and installation ensure that the KNX line is correctly dimensioned The device has a maximum current draw of 12 mA Mounting and commissioning may only be carried out by electrical specialists The applicable standards directives regulations and specifications for the country in question should be observed when planning and setting up electrical installations and securit...

Страница 62: ... Programming LED lights up after the button has been pressed It switches off as soon as ETS has assigned the physical address or the button is pressed again Download response Depending on the PC which is used the progress bar for the download may take up to one and a half minutes before it appears due to the complexity of the device Cleaning The voltage supply to the device must be switched off be...

Страница 63: ...ETS reset the device is in KNX operation The LED is off All LEDs indicate the current state Note If Manual operation is generally disabled or is disabled via communication object Block manual operation the LED flashes during the button push A switchover from KNX operation to the Manual operation mode does not occur Note If manual operation is activated the current fan speed remains set and can onl...

Страница 64: ...anual operation Flashing Changeover to KNX operation Output A Output B On Control 0 Off Control 0 Flashing Both LEDs A B or C D of an output flash in the event of overload short circuit frequency 4 8 Hz Flashing Both LEDs A B or C D of an output flash quickly simultaneously in the event of an adjustment frequency 1 2 Hz With a state change the new state is immediately indicated Output C Output D O...

Страница 65: ... Output A and C Open STOP First operation point Press Valve from 0 100 then STOP OPEN Release No reaction Output B and D Close STOP Next operation point Press Valve from 100 0 then STOP CLOSED Release No reaction Long button push 1 5 sec No function A characteristic curve adjustment is undertaken if it is parameterized Valve drive thermoelectric PWM Output A B C or D Open close First operation poi...

Страница 66: ...tch in the reverse order back to button E and then press this button again Long button push 1 5 sec No function Output H No reaction Short button push 1 5 sec Press ON Release OFF Long button push 1 5 sec No function Input a c No reaction Short button push 1 5 sec As Switch sensor and Send value Switch With every actuation the states of the input and the LED are changed Button Press button input c...

Страница 67: ...puts There are four inputs available These are used to monitor or connect the window contact condensation dew point detectors or temperature sensors for example The 6 A outputs are available for Fan Coil applications Attention Improper switching will destroy the fan motors Follow the technical data for the fan e g speed or switching function For further information see Parameter window E F G Fan M...

Страница 68: ...r supply Fan Coil units are available as recirculation or as mixed air devices Recirculation devices The room air is directed past heat exchangers by the fans Mixed air devices The room air is mixed with fresh air The mixing ratio between recirculated and fresh air can usually be adjusted 3 1 1 Functions of the inputs The following table provides an overview of the functions possible with the inpu...

Страница 69: ...es free free Analog 0 10 V 1 control value 1 valve free 2 control values 1 valve free 2 control values 2 valves Setting facilities for valve drives Thermoelectric PWM Separate heating cooling Direction OPEN CLOSE OPEN CLOSE OPEN CLOSE OPEN CLOSE Motor driven 3 point Separate heating cooling Direction OPEN CLOSE OPEN CLOSE Analog 0 10 V Separate heating cooling Direction OPEN CLOSE OPEN CLOSE Funct...

Страница 70: ...il Actuator single The following chapters describe the device parameters using the parameter windows Parameter windows are structured dynamically so that further parameters may be enabled depending on the parameterization and function of the outputs The default values of the parameters are underlined e g Options Yes No Note For screen shots the application of the FCA S 1 1 2 2 with PWM and manual ...

Страница 71: ...outputs is set to correspond with the parameterization or the communication object values If communication objects are read out via the bus during the sending and switching delay e g by a visual display system these requests are stored and a response is sent once the delay time has expired An initialization time of about two seconds is included in the delay time The initialization time is the time...

Страница 72: ...peration 1 bit Options No Send value 0 cyclically Send value 1 cyclically The communication object In operation indicates that the device on the bus is working properly This cyclic telegram can be monitored by an external device Send value 0 value 1 cyclically The value 0 or 1 is sent cyclically and the 1 bit communication object In operation is enabled Dependent parameter Telegram is repeated Opt...

Страница 73: ...nt parameter Request with object value Options 0 1 0 or 1 0 Sending status messages is requested with the value 0 1 Sending status messages is requested with the value 1 0 or 1 Sending status messages is requested with the values 0 or 1 Note If the option Yes has been selected for the parameter Enable communication object Request status values 1 bit the communication objects no 4 18 28 38 and 48 a...

Страница 74: ...on Settings for manual operation Manual operation Options Disabled Enabled Enable disable via comm object This parameter defines if the switchover between the operating states Manual operation and KNX operation is possible via the button on the device or via a communication object For further information see Manual operation p 61 Note The manual operation overwrites the input states ...

Страница 75: ...ual operation to KNX operation Options No Yes This parameter determines whether after pressing the button the device will remain in Manual operation or will be reset back to KNX operation Yes The device is reset to KNX operation Dependent parameter Time for automatic reset to KNX operation in s 1 65 535 Options 1 30 65 535 This parameter determines how long after pressing button the device will re...

Страница 76: ...nt On change The status is sent when a change occurs After request The status is sent when a request occurs After a change or request The status is sent on a change or a request For further information see Manual operation p 61 Function of the buttons Output A B blocked Output C D blocked Output E speed 1 blocked Output F speed 2 blocked Output G speed 3 blocked Input a b c Note The functions Fan ...

Страница 77: ...itch Button With this parameter the button can be disabled or programmed as a switch or push button Disabled Button disabled LEDs not functioning Switch With every actuation the states of the input and the LED are changed Button Press button input closed LED on Release button input opened LED off ...

Страница 78: ...rol value 1 valve 2 control values 1 valve 2 control values 1 valve with switching object 2 control values 2 valves 2 control values 2 valves with switching object This parameter determines how the control value is processed Note In the option 2 control values 2 valves with or without switching object one valve must be parameterized as a heating valve and the other as a cooling valve according to ...

Страница 79: ...free Setting facilities for valve drives Thermoelectric PWM Separate heating cooling Direction OPEN CLOSE OPEN CLOSE OPEN CLOSE OPEN CLOSE Control value functions Control value does not function Valves independently usable If the option Enabled as switch actuators is selected in the parameter window Enable output E H the outputs A B C and D can be used independently The individual communication ob...

Страница 80: ... processing in the device Output A Output B Output C Output D Control value input 1 control value 1 valve Control value functions Control value does not function If the option 1 control value 1 valve is selected the control value heating will operate on output A The control value fan EFG operates on the outputs E F and G To ensure correct operation of the Fan Coil the control value fan EFG is conn...

Страница 81: ... function If the option 2 control values 1 valve is selected the control values will operate on output A The two control values heating and cooling are compared internally and the larger value operates on output A valve The function of the two fans EFG control values A and B is set in the application In this example Number of control value inputs is parameterized to 2 and the reaction to Largest v...

Страница 82: ...Control value does not function If the option 2 control values 1 valve with switching object is selected the control values will operate on output A Which of the two control values operates on outputs A and C is decided via the communication object Toggle heating The function of the two fans EFG control values A and B is set in the application In this example Number of control value inputs is para...

Страница 83: ...ves is selected the control values will operate directly on output C The function of the two fans EFG control values A and B is set in the application In this example Number of control value inputs is parameterized to 2 and the reaction to Largest value To ensure correct operation of the Fan Coil the fan EFG control value A is connected with the control value cooling and the fan EFG control value ...

Страница 84: ...d the control values will operate directly on output C Which of the two control values operates on outputs A and C is decided via the communication object Toggle heating The function of the two fans EFG control values A and B is set in the application In this example Number of control value inputs is parameterized to 2 and the reaction to Largest value To ensure correct operation of the Fan Coil t...

Страница 85: ...ves Motor driven 3 point Separate heating cooling Direction OPEN CLOSE OPEN CLOSE Analog 0 10 V Separate heating cooling Direction OPEN CLOSE OPEN CLOSE Control value functions Control value does not function Valves independently usable If the option Enabled as switch actuators is selected in the parameter window Enable output E H the outputs A B C and D can be used independently The individual co...

Страница 86: ... A Output C Control value input 1 control value 1 valve Motor driven 3 point Output A B Output C D Control value input 1 control value 1 valve Control value functions Control value does not function If the option 1 control value 1 valve is selected the control value heating will operate on output A B The control value fan EFG operates on the outputs E F and G To ensure correct operation of the Fan...

Страница 87: ...ue functions Control value does not function If the option 2 control values 1 valve is selected the control values will operate on output A B The two control values heating and cooling are compared internally and the larger value operates on output A or B valve The function of the two fans EFG control values A and B is set in the application In this example Number of control value inputs is parame...

Страница 88: ...ntrol values 1 valve with switching object mean Example Valve and three speed fan Control value processing in the device Analog Output A Output C Control value input 2 control values 1 valve with switching object Motor driven 3 point Output A B Output C D Control value input 2 control values 1 valve with switching object Control value functions Control value does not function ...

Страница 89: ...uts A and C is decided via the communication object Toggle heating The function of the two fans EFG control values A and B is set in the application In this example Number of control value inputs is parameterized to 2 and the reaction to Largest value To ensure correct operation of the Fan Coil the fan EFG control value A is connected with the control value cooling and the fan EFG control value B ...

Страница 90: ...rol value input 2 control values 2 valves mean Example 2 valves and three speed fan Control value processing in the device Analog Output A Output C Control value input 2 control values 2 valves Motor driven 3 point Output A B Output C D Control value input 2 control values 2 valves Control value functions Control value does not function ...

Страница 91: ...control values A and B is set in the application In this example Number of control value inputs is parameterized to 2 and the reaction to Largest value To ensure correct operation of the Fan Coil the fan EFG control value A is connected with the control value cooling and the fan EFG control value B with the control value heating Note In the option 2 control values 2 valves with or without switchin...

Страница 92: ...rol values 2 valves with switching object mean Example 2 valves and three speed fan Control value processing in the device Analog Output A Output C Control value input 2 control values 2 valves with switching object Motor driven 3 point Output A B Output C D Control value input 2 control values 2 valves with switching object Control value functions Control value does not function ...

Страница 93: ...o fans EFG control values A and B is set in the application In this example Number of control value inputs is parameterized to 2 and the reaction to Largest value To ensure correct operation of the Fan Coil the fan EFG control value A is connected with the control value cooling and the fan EFG control value B with the control value heating Note In the option 2 control values 2 valves with or witho...

Страница 94: ... object Valve control values parallel operation is enabled Note communication object Valve control values parallel mode only operates on Fan Coil valves Note If an operation mode with 2 control values and 1 valve is selected for the Fan Coil an additional communication object no 9 is enabled that is set for cooling and is as follows depending on the operation mode of the outputs 2nd control value ...

Страница 95: ...CDC508134D0202 93 Note If the options with switching object are selected an additional parameter Toggle to heating with will appear Toggle to heating with Options 0 1 0 A telegram with the value 0 switches 1 A telegram with the value 1 switches ...

Страница 96: ...the contacts Open Close of the valve drive for opening closing the valve Individual With this setting the operation modes of outputs A and B are set individually from one another Dependent parameters Output A Output B Options Disabled Valve drive thermoelectric PWM This parameter defines the individual operation mode of the output Disabled No operation mode selected Valve drive thermoelectric PWM ...

Страница 97: ...setting the operation modes of outputs C and D are set individually from one another Dependent parameters Output C Output D Options Disabled Valve drive thermoelectric PWM This parameter defines the individual operation mode of the output Disabled No operation mode selected Valve drive thermoelectric PWM The parameter window and communication objects for the operation mode Valve drive thermoelectr...

Страница 98: ...de of the output Disabled No operation mode selected Valve drive analog 0 10 V The parameter window and communication objects for the operation mode Valve drive analog 0 10 V are enabled Valve control output A 0 10 V Valve voltage on bus voltage failure 0 volts This also applies for output C Assignment of the valves Note Outputs A and C are automatically assigned via the selection in the parameter...

Страница 99: ...option Valve drive thermoelectric PWM has been selected for the output For further information see Pulse width modulation PWM p 249 Type of valve drive de energized Options Closed Open This parameter determines the function of the valve drive Note De energized closed valve drives N C If no current flows in the valve drive the valve is closed If current flows in the valve drive the valve opens De e...

Страница 100: ... recovery in Note Control value in The actual valve setting in may diverge from the set value for control in depending on the ambient conditions e g room temperature valve drive used water pressure in the heating cooling system valve etc The set value in the parameter Control value in is based on the parameter Cycle time of PWM The output is controlled accordingly depending on the setting Example ...

Страница 101: ... displayed PWM pulse width modulation The following message appears Set cycle time PWM open closing time for contr value of valve drive in At recovery controller fault forced oper and characteristic curve Note Note Pulse width modulation With pulse width modulation the valve is operated as with 2 point control exclusively in the positions fully opened and fully closed In contrast to a 2 point cont...

Страница 102: ...mines how the received control value 0 255 can be processed The control value can be converted to a PWM signal or an ON OFF signal PWM pulse width modulated With this option the continuous control value is converted to a PWM signal The parameter for entering the PWM cycle time is displayed OPEN CLOSE Signal With this option the continuous control value is converted to an OPEN or CLOSE signal from ...

Страница 103: ...time of valve drivein s 10 6 000 Options 10 180 6 000 With this parameter a time is set in seconds that the connected valve requires to move from position 0 valve closed to position 100 valve fully open Note The time should be taken from the technical data of the valve and it corresponds with the total runtime Closing time of valve drivein s 10 6 000 Options 10 180 6 000 With this parameter a time...

Страница 104: ...alue ON OFF if the option Bit has been selected for the parameter Control value is received as or Control value continuous PWM 1 if the option Byte has been selected for the parameter Control value is received as If a control value is not received within the parameterized time a malfunction or a defective room thermostat is the cause The reaction of the output to a control value not received can b...

Страница 105: ...t Options No Yes This parameter defines the control value with a control fault No No control value is set Yes A value is set Dependent parameter Control value in 0 100 Options 0 100 This parameter determines the control value in percent used to control the output in the event of a control fault ...

Страница 106: ...e made in this parameter window Note This parameter window is visible for the products FCA S 1 1 1 2 and FCA S 1 1 2 2 These parameters appear if the option Valve drive motor driven 3 point has been selected for the outputs Reversing time Options 100 300 500 700 1 000 ms This parameter defines the reversing delay time of the valve drive Note The technical data of the valve drive must be observed ...

Страница 107: ... Active priorities override the parameterized control Dependent parameter Control value in 0 100 Options 0 100 This parameter determines the control of the output after bus voltage recovery in Valve is Options Heating valve Cooling valve This parameter determines whether the valve is defined as a heating valve or cooling valve Switch on time for valve drive from 0 to 100 in s 10 6 000 Options 10 1...

Страница 108: ... is reached the reference adjustment is started The closed position independent of the characteristic curve is then exceeded by 5 of the parameterized switch on time for the control value based on the last control value at least 1 second no more than 60 seconds This function cannot be interrupted Thereafter the currently calculated valve position is approached and the adjustment counter is set to ...

Страница 109: ...he time used to monitor the telegrams on the input control values communication objects Control value cont 3 point If a control value is not received within the parameterized time a malfunction or a defective room thermostat is the cause The reaction of the output to a control value not received can be defined in the following parameters Send object value Control value fault Options No update only...

Страница 110: ...t Options No Yes This parameter defines the control value with a control fault No No control value is set Yes A value is set Dependent parameter Control value in 0 100 Options 0 100 This parameter determines the control value in percent used to control the output in the event of a control fault ...

Страница 111: ... S 1 2 1 2 and FCA S 1 2 2 2 Control voltage with closed valve Options 0 volts 10 volts This parameter determines the function of the valve drive Note De energized closed valve drives N C If no current flows in the valve drive the valve is closed If current flows in the valve drive the valve opens De energized opened valve drives N O If no current flows in the valve drive the valve opens If curren...

Страница 112: ...meter determines the reaction of the output at bus voltage recovery Unchanged The last valve control is restored Select A value is determined Active priorities override the parameterized control Dependent parameter Control value in 0 100 Options 0 100 This parameter determines the control of the output after bus voltage recovery in ...

Страница 113: ...elegrams on the input control values communication objects Control value ON OFF if the option Bit has been selected for the parameter Control value is received as or Control value continuous PWM 1 if the option Byte has been selected for the parameter Control value is received as If a control value is not received within the parameterized time a malfunction or a defective room thermostat is the ca...

Страница 114: ...t Options No Yes This parameter defines the control value with a control fault No No control value is set Yes A value is set Dependent parameter Control value in 0 100 Options 0 100 This parameter determines the control value in percent used to control the output in the event of a control fault ...

Страница 115: ...e motor driven 3 point and Valve drive analog 0 10 V Enable function Priority and safety operation Options No Yes Yes The Parameter window Security p 117 is enabled Enable communication object Status Control value 1 bit byte Options No Yes This parameter enables the communication object Status Control value The control status of the output is sent via this communication object Yes The communicatio...

Страница 116: ...ct value is sent when a request occurs After a change or request The object value is sent when a change or request occurs Data type 1 bit byte Options Bit Byte This parameter defines the data type of the communication object Status Control value 1 bit The following parameter appears Object value with control 0 Options 0 1 If the object value at control is greater than 0 a 1 bit telegram is sent us...

Страница 117: ...ve purge 1 bit Options No Yes The status of the valve purge is displayed via this communication object Yes The 1 bit communication object Status Valve purge p 214 is enabled Dependent parameter Send object value Options No update only On change After request After a change or request No update only The object value is updated but not sent On change The object value is sent when a change occurs Aft...

Страница 118: ...1 12 is changed after the download Reset purge cycle from control value in 1 99 Options 1 99 Hereby the purge cycle is reset to the set control value if it is exceeded Note The purging cycle time is restarted if automatic valve purge has been activated at start up of the device The purging cycle time will be restarted at the end of the actual purging period The parameterized period of valve purgin...

Страница 119: ... 1 highest 3 lowest priority the output can be forcibly operated or disabled with activated function Security Forced operation The communication object Priority Forced operation is enabled Using forced operation the operation of the output is blocked and the output assumes a defined state An operation is not possible until after forced operation is rescinded Block The communication object Priority...

Страница 120: ...legram is not received within the parameterized time the output depending on the function Security set beforehand is forcibly operated or blocked If the communication object Priority Forced operation or Priority Block receives a telegram that does not correspond with the value set under Trigger with object value the monitoring time is reset and restarted 0 Cyclical monitoring is deactivated Note T...

Страница 121: ...isite The following must be considered with the characteristic curve adjustment The value pairs can be entered in any sequence They are sorted in ascending order of the control value in the device and intermediate values are interpolated If no value pair has been entered for the control value 0 the valve position of the first value pair applies for all control from 0 to the first value pair If no ...

Страница 122: ...x 1 Example Value pair 1 VP1 Value pair 2 VP2 Control value in 0 100 10 Control value in 0 100 80 Control value in 0 100 40 Control value in 0 100 20 Implemented characteristic curve Actuating value Control 0 10 40 20 37 30 34 40 31 50 29 60 26 70 23 80 100 20 ...

Страница 123: ...ons 0 100 The possibility of activating other value pairs allows different curve characteristics to be realized A total of four value pairs can be set Attention A parameterization of the value pair with the same control value leads to an undefined state and should be strictly avoided Otherwise it can lead to destruction of the HVAC system ...

Страница 124: ...tiate from those of output A or A B The descriptions of the parameter setting options and the adjustable communication objects for outputs B C and D or C D are contained in Parameter window A Output Valve drive thermoelectric PWM p 97 ff Parameter window AB Output valve drive motor driven 3 point p 104 ff or Parameter window A Output valve drive analog 0 10 V p 109 ff ...

Страница 125: ... Options Block Enabled Block Output E F G is blocked hidden No communication objects are visible Enabled The parameter window E F G Output appears Dependent communication objects become visible All parameters and their setting options for the outputs E F G do not differ from those of output H see Parameter window H Output p 163 Enable as fan The parameter window E F G Fan appears Output H Options ...

Страница 126: ...s the fan type which is to be controlled Multi level Controls a fan with up to three speeds One level Controls a fan with one speed Limit fan speeds to 2 Options No Yes The fan speeds can be limited to two here The following settings are the same as those for a three speed fan except that they apply only to two speeds No A three speed fan is controlled Yes A two speed fan is controlled via fan spe...

Страница 127: ...ly or suddenly The individual fan speeds are activated consecutively outputs switched on until the required fan speed is reached The parameterized delay time between two fan speeds has the effect that the current fan speed must be switched on for at least this time before the next speed is switched on The parameterized minimum dwell time has the same effect as a changeover switch i e it is only ac...

Страница 128: ...voltage is applied to the relay for the first time Thus damage to the device due to unintentional switch on during transport e g due to vibration is avoided It is advisable to apply a bus voltage before connecting the fan in order to assign it a defined switch state This eliminates the possibility of an incorrect contact setting destroying the fan Enable communication object Forced operation 1 bit...

Страница 129: ...on the settings set in Automatic control are ignored Automatic control is updated after forced operation has been rescinded Important Forced operation remains active until the complementary set values are sent the assignment is changed the fan type is changed Forced operation is not deactivated by a download of the application in which the fan type and the respective group addresses are retained F...

Страница 130: ...to speed 2 2 1 limited to speeds 2 and 1 2 1 OFF limited to speed 2 1 and off 3 Limited to speed 3 3 2 limited to speeds 3 and 2 3 2 1 limited to speeds 3 2 and 1 The control value is ignored Enable automatic operation Options No Yes Yes Automatic operation is enabled The Parameter window Automatic control Multi level p 137 also appears Enable direct operation Options No Yes Yes Direct operation i...

Страница 131: ... 1 bit Options No Yes The setting of a fan speed is displayed via these communication objects You can parameterize whether or not the status of a current or required fan speed is displayed Yes Three 1 bit communication objects Status Fan speed x x 1 3 are enabled Dependent parameters Meaning Options Current fan speed Required fan speed This parameter defines which status Current fan speed or Requi...

Страница 132: ...bservation i e if a limitation allows only fan speed 2 the fan is operating at fan speed 2 and for example a telegram to switch up is received the required fan speed remains at 2 as fan speed 3 cannot be reached due to the limitation Send object values Options No update only On change After request After a change or request No update only The status is updated but not sent On change The status is ...

Страница 133: ... is current fan speed The Current fan speed is the speed at which the fan is actually operating What is required fan speed The Required fan speed is the fan speed which has to be reached e g when the transition and dwell times have elapsed Note The limitations are included in this observation i e if a limitation allows only fan speed 2 the fan is operating at fan speed 2 and for example a telegram...

Страница 134: ... a 1 bit coding For further information see Status byte fan p 258 Yes The communication object Status byte fan is enabled Dependent parameter Send object value Options No update only On change After request After a change or request No update only The status is updated but not sent On change The status is sent when a change occurs After request The status is sent when a request occurs After a chan...

Страница 135: ... update only The status is updated but not sent On change The status is sent when a change occurs After request The status is sent when a request occurs After a change or request The status is sent on a change or a request The following parameter only becomes visible if the option Yes has been selected in the Enable automatic operation parameter in the Fan parameter window Enable communication obj...

Страница 136: ... on of fan speed 1 occurs is set If the value in the communication object Control value is greater than or equal to the parameterized threshold value fan speed 1 is switched on If the value is smaller then it is switched off Threshold value 1 2 in 1 100 Options 1 30 100 This sets the threshold value at which switchover to fan speed 2 occurs If the value in the communication object Control value is...

Страница 137: ...he next fan speed occurs The hysteresis applies for all three threshold values The setting 0 causes immediate switching without hysteresis The entered percentage value is directly added to or subtracted from the percentage value of Threshold value speed x The result is a new upper or lower threshold value Switch threshold top switch on threshold value hysteresis Switch threshold bottom switch off ...

Страница 138: ...ned using the control value and the set switch thresholds The hysteresis is not taken into account Control values are rounded to whole percentages by the device 3 A control variable with the value 0 always results in speed 0 An example Parameterized Threshold value OFF speed 1 10 Threshold value speed 1 speed 2 20 Threshold value speed 2 speed 3 30 Hysteresis 15 Behavior when ascending from speed ...

Страница 139: ...ed with the parameter Enable automatic operation in Parameter window E F G Fan Multi level p 124 The limits can be enabled in this parameter window Object value Automatic On Off switch on to the automatic Options 1 0 This parameter defines how the device should react to a telegram 1 Automatic is activated by a telegram with value 1 0 Automatic is activated by a telegram with value 0 ...

Страница 140: ...1 2 This parameter defines the number of control value inputs communication objects for automatic operation 1 There is only one Control value communication object 2 There are two communication objects Control value A and Control value B Dependent parameter Select by Options communication object Toggle control value A B Largest value This parameter sets how the blower actuator selects which control...

Страница 141: ...lue so that the absence of a signal e g due to a high bus load does not immediately trigger an error Where there are two control value inputs the following additional parameter appears Function of monitoring Options Monitoring current control values Monitoring active and inactive control values This parameter determines the scope of monitoring Monitoring current control values Only the currently s...

Страница 142: ...action in the event of an error Selection of option Yes Dependent parameter Control value in 0 100 Options 0 30 100 This parameter sets what percentage to use for the control value in the event of an error Reset time for automatic operation in s 1 65 535 0 inactive Options 0 1 65 535 This parameter determines after which time the automatic operation is reset 0 If 0 is selected automatic operation ...

Страница 143: ...n speed is set or may not be over undershot when forced operation is active 3 2 1 OFF All states are possible Unchanged The state is retained OFF Off 1 Limited to speed 1 1 OFF limited to speed 1 and off 2 Limited to speed 2 2 1 limited to speeds 2 and 1 2 1 OFF limited to speed 2 1 and off 3 Limited to speed 3 3 2 limited to speeds 3 and 2 3 2 1 limited to speeds 3 2 and 1 The control value is ig...

Страница 144: ...are inactive The set limitations are reactivated when automatic mode is reactivated The following points apply for limitations The fan speed and valve position can be parameterized independently The limitation need not necessarily apply to one fan speed only It can also encompass another range of the fan speeds i e only certain fan speeds can be set if the limitation is active In this way a limite...

Страница 145: ...on objects Telegram value 1 Fan speed x is switched on 0 Fan speed x is switched off If several ON OFF telegrams are received consecutively in a short period of time at various Fan speed 1 3 communication objects the value last received will be the one used to control the fan An OFF telegram to one of the three communication objects Fan speed 1 3 switches the fan off Important Forced operation rem...

Страница 146: ...ime with speed switchover remains active to protect the fan With multiple manual UP or DOWN switching the required speed will be increased or reduced by a speed step This is feasible until the maximum or minimum possible speed is reached Further UP or DOWN telegrams are ignored and not executed Each new switching telegram initiates a new calculation of the target speed This means that the target s...

Страница 147: ...p switch the previous fan speeds are switched on consecutively With the changeover switch the fan speed is switched on right away The delay between the switchover of two fan speeds contact change is taken into account The dwell times which are taken into account in automatic operation are inactive and will only be taken into account after the start up phase The start up behavior is a technical cha...

Страница 148: ...in the parameter window Automatic operation is only active and programmable if the option Yes has been selected in the Enable automatic operation parameter In the parameter window Fan you can find the parameter Enable automatic operation Important Forced operation remains valid and is taken into account The parameterized minimum fan speed dwell time for automatic control is ignored during manual o...

Страница 149: ...oes through several speed changes run on times are executed successively adding on those times A run on time of 0 seconds means that run on is deactivated Run on is executed regardless of where the speed change originates automatic operation direct operation manual procedure fan switch off Selection of option Yes Dependent parameters Run on times speed 3 in s 0 65 535 Options 0 20 65 535 Run on ti...

Страница 150: ...a two level fan set the parameters as follows In the parameter window E F G Fan select the Multi level option in the Fan type parameter Select Yes in the Limit fan speeds to 2 parameter Now a two speed fan is controlled via fan speeds 1 and 2 Fan speed 3 with all its parameters and options is now non functional Note Further parameters and their setting options are described in Parameter window E F...

Страница 151: ...Multi level One level This parameter sets which type of fan is to be controlled To control a fan with up to three speeds select the Multi level option To control a single speed fan select the One level option Fan speed on bus voltage failure Options Unchanged OFF The reaction of the fan on bus voltage failure is defined here Unchanged The fan speed remains the same OFF The fan is switched off ...

Страница 152: ...before connecting the fan in order to assign it a defined switch state This eliminates the possibility of an incorrect contact setting destroying the fan Enable automatic operation Options No Yes Yes Automatic operation is enabled The Parameter window Automatic control One level p 156 also appears Function Time on ON Options None Switching delay Minimum time This defines the Time function on Fan O...

Страница 153: ...5 The fan is switched off after this delay Selection of option Minimum time Dependent parameter Time in s 1 65 535 Options 1 20 65 535 The fan remains OFF for at least this time Enable communication object Forced operation 1 bit Options No Yes Yes A 1 bit Forced operation communication object is enabled Dependent parameters Forced operation on object value Options 0 1 0 Forced operation is activat...

Страница 154: ... No Yes From this status byte the states control values A or C automatic forced operation and the four limitations are indicated directly via a 1 bit coding For further information see Status byte fan p 258 Yes The communication object Status byte fan is enabled Dependent parameter Send object value Options No update only On change After request After a change or request No update only The status ...

Страница 155: ...t No update only The status is updated but not sent On change The status is sent when a change occurs After request The status is sent when a request occurs After a change or request The status is sent on a change or a request The following parameter is only visible if the option Yes has been selected in the Enable automatic operation parameter in the Fan parameter window Enable communication obje...

Страница 156: ...is switched on If the value is less it is switched off Hysteresis is only taken into account in automatic operation Note Hysteresis threshold value in 0 20 Options 0 5 20 This sets a hysteresis at which switchover to the next fan speed occurs The setting 0 causes immediate switching without hysteresis The entered percentage value is directly added to or subtracted from the percentage value of Thre...

Страница 157: ...ing FCA S 1 x x 1 2CDC508134D0202 155 Example a three speed fan hysteresis with fan control Using hysteresis a continuous switching between the fan speeds around the threshold value with deviating input signals can be avoided ...

Страница 158: ...ration in Parameter window E F G Fan One level p 149 This is the parameter window where you define the threshold values for switchover of the fan speed You can also enable limitations here Object value Automatic On Off switch on to the automatic Options 1 0 This parameter defines how the device should react to a telegram 1 Automatic is activated by a telegram with value 1 0 Automatic is activated ...

Страница 159: ... always selected If the values are equal but not zero the input which was the latest to receive a value is selected Activate monitoring control values Options No Yes This parameter sets the monitoring for the control value input s Any remaining telegrams on the communication object s are detected No Control value monitoring is deactivated Yes Control value monitoring is activated Dependent paramet...

Страница 160: ...endently of each other An error is reported if an object s time is exceeded Note The fault is reset if both control values are received within the monitoring time Send object value Options No update only On change After request After a change or request No update only The status is updated but not sent On change The status is sent when a change occurs After request The status is sent when a reques...

Страница 161: ...er determines after which time the automatic operation is reset 0 If 0 is selected automatic operation is not reset 1 65 535 If a time from a value of 1 is set automatic operation is reset after the given time Note A change of the parameter value will only become active after the next deactivation of automatic operation by a direct communication object ...

Страница 162: ...n speed is set or may not be over undershot when forced operation is active 3 2 1 OFF All states are possible Unchanged The state is retained OFF Off 1 Limited to speed 1 1 OFF limited to speed 1 and off 2 Limited to speed 2 2 1 limited to speeds 2 and 1 2 1 OFF limited to speed 2 1 and off 3 Limited to speed 3 3 2 limited to speeds 3 and 2 3 2 1 limited to speeds 3 2 and 1 The control value is ig...

Страница 163: ...are inactive The set limitations are reactivated when automatic mode is reactivated The following points apply for limitations The fan speed and valve position can be parameterized independently The limitation need not necessarily apply to one fan speed only It can also encompass another range of the fan speeds i e only certain fan speeds can be set if the limitation is active In this way a limite...

Страница 164: ...9 Parameter window E F G Output switch actuators The setting options of valve outputs E F and G do not differentiate from those of output H The descriptions of the parameters and communication objects for outputs E F and G are contained in Parameter window H Output p 163 ...

Страница 165: ...en contact Normally opened contact An ON telegram 1 closes the contact and an OFF telegram 0 opens the contact Normally closed contact An ON telegram 1 opens the contact and an OFF telegram 0 closes the contact Contact position on bus voltage failure Options Unchanged Open Closed The output can adopt a defined state on bus voltage failure BVF using this parameter Open The contact is opened with bu...

Страница 166: ...is redefined and set based on the set device parameterization Note Take note of the reaction on bus voltage failure recovery and download The device draws the energy for switching the contact from the bus After bus voltage is applied it takes about ten seconds before sufficient energy is available to switch all contacts simultaneously Depending on the transmission and switching delay on bus voltag...

Страница 167: ...st occurs After a change or request The status is sent on a change or a request Object value of contact position Options 1 closed 0 open 0 closed 1 open This parameter defines the communication object value of the switch status Status switch 1 Closed 0 Open A closed contact is represented by communication object value 1 and an open contact is represented by the value 0 0 Closed 1 Open A closed con...

Страница 168: ...er window H Output p 163 Explanations of the Time functions and sequences can be found in Planning and application p 237 ff Also observe the Function diagram p 245 which indicates the switching and sequence priorities Time function Staircase light Staircase lighting The value that switches the staircase lighting on and off can be parameterized The staircase lighting time starts when the function i...

Страница 169: ...eterized maximum time may not be exceeded No not retriggerable The receipt of an ON telegram is ignored The staircase lighting time continues unmodified to completion Yes retriggerable New ON telegrams reset the staircase lighting time and starts to count again This process can be repeated as often as desired using this selection Up to max 2 3 4 5 x staircase lighting time New ON telegrams extend ...

Страница 170: ... a download Options Unchanged 0 enable function Time 1 Disable function Time This parameter defines how the function Time should react after a download With a telegram to the communication object Disable function Time the function Time can be disabled Unchanged The function Time can continue unchanged Note The state of the Time function is stored with bus voltage failure and continues unchanged af...

Страница 171: ...t How does the staircase lighting react on bus voltage recovery Reaction on bus voltage recovery is defined by two conditions 1 By the communication object Disable function time If staircase lighting is disabled after bus voltage recovery it can only be switched on or off via the communication object Switch 2 By the parameterization of the communication object Switch Whether the light is switched ...

Страница 172: ...PT100 2 cond technology 50 150 C PT1000 2 cond technology 50 150 C KTY 50 150 C The operating mode of the input is set with this parameter The respective parameter window a xxx also becomes visible with the selection of an operating mode Description 40 characters With this parameter it is possible to enter a text of up to 40 characters in length for identification in the ETS Note The text which is...

Страница 173: ... several inputs However as the functions for all inputs are identical only the functions of input a will be described Maximum dead time This parameter is fixed to a preset 250 ms The maximum dead time prevents unwanted multiple operations of the input e g due to bouncing of the contact What is the maximum dead time An edge change at the input is assessed with a maximum dead time delay value of 250...

Страница 174: ...ction between long and short operation Options No Yes Using this parameter you set if the input differentiates between short and long operation Yes After opening closing the contact it must first of all be ascertained if a short or long operation has occurred here Only thereafter will a possible reaction be triggered The following table shows the function in detail TL is the time duration from whe...

Страница 175: ...istinction between long and short operation the following parameters appear in Parameter window a Switch sensor p 171 Opening the contact Event 0 Closing the contact Event 1 NOTE Activate minimum signal duration Options No Yes Selection Yes Dependent parameters On closing the contact in 0 65 535 X 0 1 s Options 0 10 65 535 On opening the contact in 0 65 535 x 0 1 s Options 0 10 65 535 ...

Страница 176: ... a further edge appears at the input during the minimum signal duration it will be interpreted as a new operation and the minimum signal duration restarts If no further edges occur after the start of the minimum signal duration a telegram is sent on the bus after the minimum signal duration has timed out Example Minimum signal duration of the input signal for a detected edge In only two cases do n...

Страница 177: ...o the actual adjustable sending delay time This can be set separately Enable communication object Start event 0 1 1 bit Options Yes No Yes The 1 bit communication object Start event 0 1 is enabled As a result the same events such as those of the push button switch connected to the binary input can also be triggered by the receipt of a telegram on the communication object Start event 0 1 Enable com...

Страница 178: ...ge evaluation ON OFF Toggle Terminate cyclic transmission The reaction of the communication object is determined here If the option Yes has been selected with the parameter Distinction between long and short operation the reaction occurs with a short or long operation With the option No it occurs with each edge change Important If the option Terminate cyclic transmission is set it is important to ...

Страница 179: ...ated together with the communication object Switch 1 of the input Attention If an internal connection with an output is selected and at the same time the reaction to an event is parameterized with toggle the communication object Switch 1 of the input is updated with the inverted value of the communication object Status Switch of the output Ensure that the communication object Status Switch of the ...

Страница 180: ...ing so that they cannot be changed via the bus If this functionality is required irrespectively these flags should be set accordingly When the communication object Switch changes and after bus recovery after the sending delay time has elapsed the communication object value is sent immediately on the bus and the sending cycle time restarts Selection Yes Dependent parameters Telegram is repeated Opt...

Страница 181: ...Internal connection Options No Output E Output F Output G Output H With this parameter a direct connection of the input with an output can be established With this connection no assignment of the group address is necessary Output E H The communication object Switch of the output is updated together with the communication object Switch 2 3 of the input Attention If an internal connection with an ou...

Страница 182: ...Input on operation Options open Closed Open The input is opened with actuation Closed The input is closed with actuation If a normally open contact is connected to the input the option Closed should be selected on a normally closed contact the option Open should be selected Long operation after Options 0 6 0 8 s 1 1 2 1 5 s 2 3 4 5 6 7 8 9 10 s Here the time period TL after which an operation is c...

Страница 183: ... has been selected in the parameter Input a in Parameter window Enable inputs a c p 170 Maximum dead time This parameter is fixed to a preset 250 ms The maximum dead time prevents unwanted multiple operations of the input e g due to bouncing of the contact What is the maximum dead time An edge change at the input is assessed with a maximum dead time delay value of 250 ms This time may vary from 0 ...

Страница 184: ...ignored for the maximum dead time TD Enable communication object Block 1 bit Options No Yes Yes The 1 bit block communication object Block is enabled This can be used to disable the input Notes If the input is disabled and the option Send cyclically is set the last state is still sent regardless of the block The option Block still blocks the physical input sending continues internally ...

Страница 185: ...of all be ascertained if a short or long operation has occurred here Only thereafter will a possible reaction be triggered Note With distinction between long and short operation two communication objects are visible for each input One communication object only transmits during short operation the other communication object only during a long operation The following table shows the function in deta...

Страница 186: ...ction between long and short operation the following parameters appear in Parameter window a Value forced operation p 181 Opening the contact Event 0 Closing the contact Event 1 NOTE Activate minimum signal duration Options No Yes Selection Yes Dependent parameters On closing the contact in 0 65 535 X 0 1 s Options 0 10 65 535 On opening the contact in 0 65 535 x 0 1 s Options 0 10 65 535 ...

Страница 187: ... a further edge appears at the input during the minimum signal duration it will be interpreted as a new operation and the minimum signal duration restarts If no further edges occur after the start of the minimum signal duration a telegram is sent on the bus after the minimum signal duration has timed out Example Minimum signal duration of the input signal for a detected edge In only two cases do n...

Страница 188: ...ad ETS reset and bus voltage recovery The following parameter appears Inactive wait state after bus voltage recovery in s 0 65 535 Options 0 65 535 Here the waiting time after a bus voltage recovery is set After the waiting time has elapsed the state on the input terminals is scanned The input reacts as if the state on the input terminals has just changed Note The inactive waiting time does not ad...

Страница 189: ... rounding off errors can occur meaning that the value sent to the bus may not correspond precisely to the set value If a high degree of precision is required select the option 4 byte value floating point Depending on the selection made in the parameter Value 1 different parameters will appear All parameters are described in the following Sent value X Options ON OFF TOGGLE 0 1 128 0 127 0 255 32 76...

Страница 190: ... via the Switch communication object The binary input controls the actuator via the Switch communication object The actuator is switched off Bit 0 of the value of the Forced operation communication object is evaluated 1 1 On The communication object Switch of the actuator is disabled by the binary input The assigned sensor cannot control the actuator via the Switch communication object The binary ...

Страница 191: ...i bus KNX Commissioning FCA S 1 x x 1 2CDC508134D0202 189 Value 2 event 1 or on long operation Note The options and parameter descriptions of the parameter Value 2 correspond with those of parameter Value 1 ...

Страница 192: ...tion Yes If the option Yes is selected with the parameter Distinction between long and short operation the following parameters appear Short operation Event 0 Long operation Event 1 NOTE Note The remaining parameter descriptions can be found in the chapter Parameter Distinction between long and short operation No page 184 ...

Страница 193: ...1000 has been selected in the parameter Input a in Parameter window Enable inputs a c p 170 The Sensor output is set with these parameters The data can be found in the sensor manufacturer s technical documentation Send output value as This parameter is fixed to 2 byte EIB floating point What is the output value The Analogue Input records a sensor measured value converts it according to the set par...

Страница 194: ...easurements High mean value over 64 measurements This parameter is used for setting a filter floating mean value filter This can be used to set the output value as a mean value using three different options Inactive Filter is not active Low Mean output value over 4 measurements Medium Mean output value over 16 measurements High Mean output value over 64 measurements Important By use of the filter ...

Страница 195: ...nge The output value is sent when a change occurs Cyclically The output value is sent cyclically On change and cyclically The output value is sent cyclically when a change occurs Selection of options On change cyclically and On change and cyclically Dependent parameters Output value is sent from a change of x 0 1 C Options 1 10 200 This parameter defines from which temperature change the output va...

Страница 196: ... can be made here e g setting the hysteresis and thresholds If Yes is selected the communication object Threshold 1 Input a appears Use Threshold 2 Options No Yes No The parameter window remains disabled and invisible Yes The Threshold 2 parameter window appears After the Threshold function has been enabled the parameter window a Threshold 2 is enabled Further settings can be made here e g setting...

Страница 197: ... 10 7 11 7 13 7 KTY 21 5 23 5 KTY 21 6 23 6 KTY 21 7 23 7 KTY 81 110 81 120 81 150 KTY 82 110 82 120 82 150 KTY 81 121 82 121 KTY 81 122 82 122 KTY 81 151 82 151 KTY 81 152 82 152 KTY 81 210 81 220 81 250 KTY 82 210 82 220 82 250 KTY 81 221 82 221 KTY 81 222 82 222 KTY 81 251 82 251 KTY 81 252 82 252 KTY 83 110 83 120 83 150 KTY 83 121 KTY 83 122 KTY 83 151 User defined For selection of a predefin...

Страница 198: ...istance values as visible for the preset values must be in ascending order An incorrect entry can lead to unrealistic output values Resistance in ohms at 50 150 C Options 0 1 030 4 280 5 600 A resistance characteristic can be entered via these 11 parameters The data can be found in the sensor manufacturer s technical documentation Note The description of the further parameters can be found in the ...

Страница 199: ...f the connected temperature sensor Important The maximum cable length permitted between the sensor and device input is 30 m Cross section of conductor Value 0 01 mm2 1 150 Options 1 100 150 150 1 5 mm2 The cross section of the conductor to which the temperature sensor is connected is entered using this parameter Important Line fault compensation via cable length is only suitable for copper conduct...

Страница 200: ...e in milliohms total of forw and ret conduct Options 0 500 10 000 Using this parameter the level of cable resistance of the connected temperature sensor is set Important In order to correctly measure the cable resistance the conductors must be shorted together at the end of the cable and should not be connected to the Analogue Input ...

Страница 201: ...llowing details also apply to Threshold 2 Tolerance band lower limit Input in 0 1 C Options 500 1500 Tolerance band upper limit Input in 0 1 C Options 500 1500 The upper and lower limits of the tolerance band are set via these two parameters The entry is made in steps of 0 1 C i e an entry of 1500 means 150 C ...

Страница 202: ...er Send output value as 1 bit or 1 byte Options 1 bit 1 byte 0 255 Selection of option 1 bit Dependent parameters Send if threshold fallen below Send if threshold exceeded Options No telegram ON telegram OFF telegram No telegram No reaction occurs ON telegram A telegram with the value 1 is sent OFF telegram A telegram with the value 0 is sent Min duration of the undershoot Min duration of the over...

Страница 203: ...255 Options 0 255 A value of 0 to 255 can be entered in single steps Min duration of the undershoot Min duration of the overshoot Options None 5 10 30 60 seconds 2 3 5 10 30 60 minutes 2 3 5 10 12 24 hours None the threshold is sent directly With the further time options a minimum duration can be selected If the send condition reverts during the minimum duration no telegram is sent ...

Страница 204: ...ent when a change occurs On change and cyclically The threshold object is sent cyclically when a change occurs The threshold object is sent cyclically until the value falls below or exceeds the other limit Dependent parameters Cycle time if lower threshold fallen below Cycle time if upper threshold exceeded Options None 5 10 30 60 seconds 2 3 5 10 30 60 minutes 2 3 5 10 12 24 hours These two param...

Страница 205: ...2nd control value cooling analog 0 10 V Output A 5 001 1 byte x x 10 Control value heating ON OFF Output A 1 001 1 bit x x Control value heating continuous PWM Output A 5 001 1 byte x x Control value heating continuous 3 point Output A B 5 001 1 byte x x Control value heating analog 0 10 V Output A 5 001 1 byte x x 11 Status Control value Output A Output A B 5 001 1 byte x x x Status Control value...

Страница 206: ... Commissioning 204 2CDC508134D0202 FCA S 1 x x 1 No Functionality Name Data Point Type DPT Length Flags C R W T U 20 29 Output B CO as for output A 30 39 Output C CO as for output A 40 49 Output D CO as for output A ...

Страница 207: ...tus Fan speed 3 Fan EFG Multi level 1 001 1 bit x x x 60 Switch Output F 1 001 1 bit x x Run on Fan EFG Multi level 1 003 1 bit x x 61 Limitation 1 Fan EFG 1 003 1 bit x x Permanent on Output F 1 003 1 bit x x 62 Limitation 2 Fan EFG 1 003 1 bit x x Disable function Time Output F 1 003 1 bit x x 63 Limitation 3 Fan EFG 1 003 1 bit x x Status Switch Output F 1 001 1 bit x x x 64 Limitation 4 Fan EF...

Страница 208: ...nsor 1 001 1 bit x x x Value 2 Input a Value forced operation Variable x x Measured value out of range Input a Temperature sensor 1 001 1 bit x x x 93 Switch 3 Input a Switch sensor 1 001 1 bit x x x Threshold 1 Input a Temperature sensor Variable x x x 94 Start event 0 1 Input a Switch sensor 1 001 1 bit x x Change Threshold 1 lower limit Input a Temperature sensor Variable x x x 95 Change Thresh...

Страница 209: ...unication objects are sent on the bus as long as these have not been programmed with the option On change After request or After a change or request Option x 1 produces the following function Telegram value 1 All status messages are sent 0 No reaction 2 Block manual operation General 1 bit DPT 1 003 C W The communication object is enabled if the parameter Manual operation has been selected with th...

Страница 210: ...s disrupted Note In the event of a fault Internal communication fault no values are sent if the option After request is selected Bit 2 Status Input c Measured value out of range 0 1 in range out of range Bit 1 Status Input b Measured value out of range 0 1 in range out of range Bit 0 Status Input a Measured value out of range 0 1 in range out of range If the option Yes has been selected for the pa...

Страница 211: ...2 and FCA S 1 2 2 2 The communication object is always visible Telegram value 0 No fault on the output 1 Fault on the output 6 Reset malfunction Output A Output A B 1 bit DPT 1 015 C W T A fault is reset via this communication object e g short circuit overload LED flashes on the device Note Signaling via LED occurs only for the devices FCA S 1 1 2 2 and FCA S 1 2 2 2 A reset is only successful if ...

Страница 212: ... communication object value 255 the output switches ON permanently valve is fully open with normally open valve drive Telegram value 0 OFF valve drive closed x Intermediate values 255 ON valve drive opened 9 2nd control value cooling continuous 3 point Output A B 1 byte DPT 5 001 C R This group operation is enabled if a Fan Coil operating mode with two control values and one valve has been selecte...

Страница 213: ...h the option Byte in Parameter window A Output Valve drive thermoelectric PWM p 97 The communication object value 0 255 determines the variable mark to space ratio of the valve drive With communication object value 0 the output switches OFF valve is closed with normally closed valve drive With communication object value 255 the output switches ON permanently valve is fully open with normally open ...

Страница 214: ... request or After a change or request the value of the communication object has changed and the parameter is set to After request or After a change or request a read request is carried out on this communication object Telegram value 0 255 Control is displayed directly as a figure value At 0 LED yellow off At 0 LED yellow on 11 Status Control value Output A Output A B 1 bit DPT 1 011 C R T This com...

Страница 215: ... C W This communication object is enabled with the option Yes via the parameter Enable valve purge in Parameter window Function p 113 The valve purge is enabled via this communication object Telegram value 0 End valve purge valve will be closed 1 Start valve purge valve will be opened The purging cycle time is restarted if automatic valve purge has been activated at start up of the device The purg...

Страница 216: ...15 Priority 1 Forced operation Output A Output A B 1 bit DPT 1 001 C W This communication object is enabled if the parameter Safety priority 1 has been selected with the option Forced operation 1 bit object in Parameter window Security p 117 If a telegram with the value 1 or 0 is received can be parameterized the output is forcibly operated and the operation is blocked The reaction of the output w...

Страница 217: ...current 0 1 No overload short circuit Overload short circuit current Bit 3 Manual operation active 0 1 Manual operation inactive Manual operation active Bit 2 Safety priority 1 2 3 forced operation or block 0 1 None active At least one active Bit 1 Purging 0 1 No valve purge Valve purge active Bit 0 Status output control value 0 0 1 Control value 0 output OFF Control value 0 output ON For further ...

Страница 218: ...ration Limitations through forced operation or one of the four limitations 1 4 are retained Automatic operation is disabled communication object Automatic ON OFF reactivates automatic operation The thresholds set in the parameter window Thresholds that define the fan speeds 1 2 and 3 are valid Telegram value 0 Fan OFF 1 255 Fan ON 50 Switch speed Fan E F G 1 byte DPT 5 010 C W This communication o...

Страница 219: ...in Parameter window E F G Fan Multi level p 124 and the parameter Enable communication object Fan speed up down 1 bit has been selected with the option Yes in Parameter window Direct operation Multi level p 143 With this communication object the fan can be switched one fan speed further up or down via a 1 bit telegram Switching up down is determined by the telegram value With multiple manual up or...

Страница 220: ... speed 2 3 03 00000011 Fan speed 3 57 Status Fan speed 1 Fan E F G 1 bit DPT 1 001 C R T This communication object is enabled if the parameter Enable communication object Status Fan speed x 1 byte has been selected with the option Yes in Parameter window Status messages Multi level p 129 You can parameterize whether the communication object value is updated but not sent sent on request or only sen...

Страница 221: ...ve in automatic operation The limitation 1 is active if a telegram with the value 1 is received on the communication object Limitation 1 The Limitation 1 is deactivated if a telegram with the value 0 is received on the communication object Limitation 1 When Limitation 1 is activated the fan can only assume the fan speed or speed range as set in the parameter Limitation 1 Telegram value 0 Limitatio...

Страница 222: ...m on this communication object Automatic mode is switched off if a telegram is received on a manual communication object Manual communication objects are Fan Switch speed Fan Switch speed x x 1 2 or 3 Fan Fan speed up down Fan Limitation x x 1 2 3 or 4 During forced operation automatic mode remains active but operates only within the allowed limits If the value 1 is set in the parameter Telegram v...

Страница 223: ...displayed or sent on the bus via this communication object You can parameterize whether the communication object value is updated but not sent sent on request or only sent when changed Telegram values Bit sequence 76543210 Bit 7 Forced operation 0 1 Inactive Active Bit 6 Limitation 1 0 1 Inactive Active Bit 5 Limitation 2 0 1 Inactive Active Bit 4 Limitation 3 0 1 Inactive Active Bit 3 Limitation ...

Страница 224: ...d as a 1 byte value 0 255 71 Toggle control value A B if 2 control values Fan E F G 1 bit DPT 1 001 C W This communication object is enabled if two communication objects have been activated for the control values control value A and control value B in Parameter window Automatic control Multi level p 137 and they are to be selected by a communication object 72 Fault control value Fan E F G 1 bit DP...

Страница 225: ...an An OFF command switches the fan off Telegram value 0 Fan OFF 1 Fan ON 52 54 Not assigned 55 Status Fan ON OFF Fan E F G 1 bit DPT 1 001 C R T This communication object is enabled if the parameter Enable communication object Status Fan On Off 1 bit has been selected with the option Yes in Parameter window Status messages single speed p 152 The communication object receives the communication obje...

Страница 226: ...on object Limitation 1 When Limitation 1 is activated the fan can only assume the fan speed or speed range which has been set in the parameter window Limitation 1 Telegram value 0 Limitation x inactive 1 Limitation x active 62 Limitation 2 See communication object 61 63 Limitation 3 See communication object 61 64 Limitation 4 See communication object 61 65 Forced operation Fan E F G 1 bit DPT 1 00...

Страница 227: ... up down Fan Limitation x x 1 2 3 or 4 During one of the four limitations or forced operation automatic mode remains active but operates only within the allowed limits If the value 1 is set in the parameter Telegram value 0 Automatic operation OFF 1 Automatic operation ON If the value 0 is set in the parameter Telegram value 0 Automatic operation ON 1 Automatic operation OFF 67 Status Automatic Fa...

Страница 228: ...displayed or sent on the bus via this communication object You can parameterize whether the communication object value is updated but not sent sent on request or only sent when changed Telegram values Bit sequence 76543210 Bit 7 Forced operation 0 1 Inactive Active Bit 6 Limitation 1 0 1 Inactive Active Bit 5 Limitation 2 0 1 Inactive Active Bit 4 Limitation 3 0 1 Inactive Active Bit 3 Limitation ...

Страница 229: ... as a 1 byte value 0 255 71 Toggle control value A B if 2 control values Fan E F G 1 bit DPT 1 001 C W This communication object is enabled if two communication objects have been activated for the control values control value A and control value B in Parameter window Automatic control One level p 156 and they are to be selected by a communication object 72 Fault control value Fan E F G 1 bit DPT 1...

Страница 230: ...o Functionality communication object name Data type Flags 50 53 Output E communication objects for output E See communication objects 80 83 output H communication objects Output F No Functionality communication object name Data type Flags 60 63 Output F communication objects for output F See communication objects 80 83 output H communication objects Output G No Functionality communication object n...

Страница 231: ...in Parameter window Time p 166 This communication object can be used for example to allow service or maintenance and cleaning personnel to initiate a permanent ON The device receives a switch telegram via the switch object Permanent ON becomes inactive after a download or bus voltage recovery Telegram value 1 Activates permanent ON mode 0 Deactivates permanent ON mode 82 Disable function Time Outp...

Страница 232: ... not differentiate from one another and are explained using Input a The descriptions of the parameter setting options of Inputs a c are contained in Parameter window Inputs a c p 170 The communication objects Input a have the nos 90 99 The communication objects Input b have the nos 100 109 The communication objects Input c have the nos 110 119 ...

Страница 233: ...s to immediate sending of the new communication object value after enabling If the input state remains the same during the blocking phase the communication object value is not sent Telegram value 0 Enable input a 1 Block input a 91 Switch 1 Input a Switch sensor 1 bit DPT 1 001 C W T This communication object is enabled if the parameter Input a has been selected with the option Switch sensor in Pa...

Страница 234: ...1 1 bit has been selected with the option Yes in Parameter window a Switch sensor p 171 The 1 bit communication object Start event 0 1 is enabled As a result the same events except those of the push button switch connected to the binary input can also be triggered by the receipt of a telegram on the communication object Start event 0 1 Telegram value 0 Start event 0 1 Start event 1 95 99 Not assig...

Страница 235: ...he block leads to immediate processing e g The minimum actuation or detection of a long short button push starts communication objects send their current value if necessary Telegram value 0 Enable input a 1 Block input a 91 Value 1 Input a Value forced operation DPT variable C T This communication object is enabled if the parameter Input a has been selected with the option Value forced operation i...

Страница 236: ... short circuit detection of the sensor The check is repeated with every measurement When is the value of the communication object sent Measured value out of range is sent if the measured value exceeds the lower or upper limit by more than 5 The following must be observed particularly with the lower limit This only applies if the lower limit of 0 is different If the lower limit is 0 it is not possi...

Страница 237: ...mperature sensor Variable DPT variable C R T 95 Change Threshold 1 upper limit Input a Temperature sensor Variable DPT variable C R T The upper and lower limits of threshold 1 can be changed via the bus The data type of these communication objects depends on the set data type of the communication object Output value Input a Important The lower limit should be selected to be lower than the upper li...

Страница 238: ...g decides whether to use heating or cooling mode Telegram value 0 Heating 1 Cooling 121 Valve control values parallel mode General 1 bit DPT 1 100 C W If a fan coil operating mode with two control values and two valves is selected in Parameter window Enable output A D p 76 the parameter communication object Valve control values parallel mode 1 bit will appear If the option Yes is selected for this...

Страница 239: ... chapter you will find some tips and application examples for practical use of the device Application examples and practical tips on the topic of temperature control valve drives characteristic curve adjustment etc can be found in the Application manual Heating Ventilation Air Conditioning at www abb com knx ...

Страница 240: ...d In combination with a valve control 2 3 or 4 pipe system can be implemented The fans are controlled via a 3 stage speed controller For this purpose three windings are tapped off the fan motor The resulting fan speed is dependent on the tapping selected It must be ensured that two contacts are not switched on simultaneously For control purposes at least one 3 stage changeover switch with zero pos...

Страница 241: ...natively fan control can be implemented via a 1 byte communication object Switch speed or via the communication object Fan speed up down Some ventilation controls require an additional central switch on mechanism main switch in addition to the speed switch Another output of the device may be used for this The output must be linked to the communication object Status Fan ON OFF This will switch on t...

Страница 242: ... 0 0 Fan speed 1 1 0 0 Fan speed 2 1 1 0 Fan speed 3 1 1 1 The step switch cannot be switched on rapidly If for example fan speed 3 is to be switched on from the OFF state fan speeds 1 and 2 must be controlled with the associated dwell times first 4 1 2 Automatic operation With automatic fan control a fan drive is connected directly to the device and switched via three floating contacts A single s...

Страница 243: ...ration Depending on the HVAC system this is set in the parameter window Control input and the control value communication objects are enabled An automatic operation parameterized in the ETS only becomes active after the first download Automatic mode is switched off either by a manual setting command via the communication objects Speed x Switch speed or Fan speed up down or if a telegram with the v...

Страница 244: ...mal Binary value bit 76543210 Fan speed 0 00 00000000 0 OFF 1 01 00000001 Fan speed 1 2 02 00000010 Fan speed 2 3 03 00000011 Fan speed 3 3 03 00000011 Values greater than 3 are ignored 4 1 4 Switchover between automatic and direct operation The device can be switched between automatic operation and direct operation The changeover to manual fan control is implemented via a 1 bit value The fan spee...

Страница 245: ...shows the speed changeover logic for the device depending on the control values and the parameterized threshold values and hysteresis values The diagram relates to a three speed fan without parameterized fan limitations The fan limitations are only relevant after the fan speed has been determined and do not change the flow chart ...

Страница 246: ...1 6 Fan operation functional diagram The following illustration indicates the sequence in which the fan control functions are processed communication objects which lead to the same box have the same priority and are processed in the sequence in which the telegrams are received ...

Страница 247: ...cessed communication objects which lead to the same box have the same priority and are processed in the sequence in which the telegrams are received Note When the communication object Switch receives a telegram the result of that telegram serves as an input signal for the Time function If that function is not disabled a corresponding switch signal is generated Subsequently the switching action is ...

Страница 248: ...ight After the staircase lighting time TON has elapsed the output switches off automatically For every telegram with the value 1 the staircase lighting time restarts unless the parameter Extending staircase lighting time by multiple operation Pumping up is set to No not retriggerable in Parameter window Time p 166 The reaction is the basic reaction of the Staircase lighting function Via pumping up...

Страница 249: ...nductor switched phase for OPEN switched phase for CLOSE Using 3 point valve drives the valve can be opened to any desired percentage and the position can be retained over an extended period If the valve is not moved no voltage is applied to the motor The valve is opened wide enough to allow the exact quantity of hot or cold water to flow that is required to bring the heat exchanger to the require...

Страница 250: ... the temperature The valve is brought to a position which complies with the calculated control value With this method the valve can be fully opened fully closed and even positioned in every intermediate position Continuous control is the most precise form of temperature control At the same time the positioning frequency of the valve drive can be kept low Continuous control can be implemented with ...

Страница 251: ...e is fixed for a timed cycle and recalculated in the duration for valve opening The control value 20 at a cycle time of 15 minutes for example will be recalculated for a valve opening time of three minutes The control value 50 results in a valve opening time of 7 5 minutes With pulse width modulation a relatively accurate setting of the temperature can be achieved without any resulting overshoots ...

Страница 252: ...ulation is converted into a signal for a 2 point control ON OFF ON With PWM control the received control value 0 100 calculated in the control algorithm is converted to a pulse width modulation The conversion is based on a constant cycle time If the device for example receives a control value of 20 then for a cycle time of 15 minutes the valve will be opened for three minutes 20 of 15 minutes and ...

Страница 253: ...lation calculation With pulse width modulation control is implemented by a variable mark space ratio During the time tON the valve is opened and during the time tOFF it is closed On account of tON 0 4 x tCYC the valve is set to about 40 on tCYC is the so called PWM cycle time for continuous control ...

Страница 254: ...verload short circuit and supply voltage recovery Switch off is not taken into account in the status objects After switch off the outputs assume the current state 4 4 1 Bus voltage recovery Fan or switch actuator reaction to bus voltage failure can be set 4 4 2 Bus voltage recovery A fan speed value can be predefined for bus voltage recovery In Switch actuator mode the communication object Switch ...

Страница 255: ...function Reset device This stops and restarts the application 4 4 4 Download During a download the output behaves just as it would on bus voltage failure Note After a download with a change the parameter reacts as if there has been an ETS reset If the application is downloaded again full download after a full discharge the reaction is the same as after an ETS reset After the application is removed...

Страница 256: ...tion 7 Bus voltage recovery Switch Actuator The priorities for telegram processing are defined as follows 1 Bus voltage failure 2 Function Time Staircase lighting 3 Switching telegrams 4 Bus voltage recovery Output A B C and D The priorities for telegram processing are defined as follows 1 Manual operation if active 2 Parameterized valve position after bus voltage recovery 3 communication object B...

Страница 257: ...vered items should be checked against the list below 1 x Fan Coil Actuator alternatively FCA S 1 1 1 2 Fan Coil Actuator PWM MDRC FCA S 1 2 1 2 Fan Coil Actuator 0 10V MDRC FCA S 1 1 2 2 Fan Coil Actuator PWM Manual Operation MDRC FCA S 1 2 2 2 Fan Coil Actuator 0 10V Manual Operation MDRC 1 x installation and operating instructions 1 x bus connection terminal red black ...

Страница 258: ... 10 102 66 188 BC 17 11 103 67 189 BD 18 12 104 68 190 BE 19 13 105 69 191 BF 20 14 106 6A 192 C0 21 15 107 6B 193 C1 22 16 108 6C 194 C2 23 17 109 6D 195 C3 24 18 110 6E 196 C4 25 19 111 6F 197 C5 26 1A 112 70 198 C6 27 1B 113 71 199 C7 28 1C 114 72 200 C8 29 1D 115 73 201 C9 30 1E 116 74 202 CA 31 1F 117 75 203 CB 32 20 118 76 204 CC 33 21 119 77 205 CD 34 22 120 78 206 CE 35 23 121 79 207 CF 36...

Страница 259: ...15 107 6B 193 C1 22 16 108 6C 194 C2 23 17 109 6D 195 C3 24 18 110 6E 196 C4 25 19 111 6F 197 C5 26 1A 112 70 198 C6 27 1B 113 71 199 C7 28 1C 114 72 200 C8 29 1D 115 73 201 C9 30 1E 116 74 202 CA 31 1F 117 75 203 CB 32 20 118 76 204 CC 33 21 119 77 205 CD 34 22 120 78 206 CE 35 23 121 79 207 CF 36 24 122 7A 208 D0 37 25 123 7B 209 D1 38 26 124 7C 210 D2 39 27 125 7D 211 D3 40 28 126 7E 212 D4 41 ...

Страница 260: ... 196 C4 25 19 111 6F 197 C5 26 1A 112 70 198 C6 27 1B 113 71 199 C7 28 1C 114 72 200 C8 29 1D 115 73 201 C9 30 1E 116 74 202 CA 31 1F 117 75 203 CB 32 20 118 76 204 CC 33 21 119 77 205 CD 34 22 120 78 206 CE 35 23 121 79 207 CF 36 24 122 7A 208 D0 37 25 123 7B 209 D1 38 26 124 7C 210 D2 39 27 125 7D 211 D3 40 28 126 7E 212 D4 41 29 127 7F 213 D5 42 2A 128 80 214 D6 43 2B 129 81 215 D7 44 2C 130 82...

Страница 261: ... 1 pcs kg Packaging pcs FCA S 1 1 1 2 Fan Coil Actuator PWM MDRC 2CDG110195R0011 942195 0 1 1 FCA S 1 1 2 2 Fan Coil Actuator PWM Manual Operation MDRC 2CDG110194R0011 942188 0 1 1 FCA S 1 2 1 2 Fan Coil Actuator 0 10V MDRC 2CDG110196R0011 942225 0 1 1 FCA S 1 2 2 2 Fan Coil Actuator 0 10V Manual Operation MDRC 2CDG110193R0011 942171 0 1 1 ...

Страница 262: ...ABB i bus KNX Appendix 260 2CDC508134D0202 FCA S 1 x x 1 A 6 Notes ...

Страница 263: ......

Страница 264: ...the contents of this document without prior notice The agreed properties are definitive for any orders placed ABB AG shall not be liable for any consequences arising from errors or incomplete information in this document We reserve all rights in the Document and in the subject matter and illustrations contained therein Reproduction transfer to third parties or processing of the content including s...

Отзывы: