ABB i-bus
®
KNX
Commissioning
FCA/S 1.x.x.1 | 2CDC508134D0202 79
Fan Coil operating mode: 2 control values/1 valve
What does the option control value input "2 control values/1 valve" mean?
Example: Valve and three-speed fan
Control value processing in the device
Output A
Output B
Output C
Output D
Control value input
2 control values/1 valve
-
-
-
= Control value functions
- = Control value does not function
If the option
2 control values/1 valve
is selected, the control values will operate on output A.
The two control values, heating and cooling, are compared internally and the larger value operates on
output A (valve).
The function of the two fans EFG control values A and B is set in the application. In this example, "Number
of control value inputs" is parameterized to 2 and the reaction to "Largest value".
To ensure correct operation of the Fan Coil, the fan EFG control value A is connected with the control
value cooling and the fan EFG control value B with the control value heating.
Содержание i-bus KNX
Страница 1: ...ABB i bus KNX Fan Coil Actuators FCA S Product Manual ...
Страница 2: ......
Страница 6: ......
Страница 12: ......
Страница 24: ...ABB i bus KNX Device technology 22 2CDC508134D0202 FCA S 1 x x 1 2 1 12 Dimension drawing 2CDC072016F0013 ...
Страница 36: ...ABB i bus KNX Device technology 34 2CDC508134D0202 FCA S 1 x x 1 2 2 12 Dimension drawing 2CDC072031F0011 ...
Страница 48: ...ABB i bus KNX Device technology 46 2CDC508134D0202 FCA S 1 x x 1 2 3 11 Dimension drawing 2CDC072015F0013 ...
Страница 60: ...ABB i bus KNX Device technology 58 2CDC508134D0202 FCA S 1 x x 1 2 4 11 Dimension drawing 2CDC072015F0012 ...
Страница 262: ...ABB i bus KNX Appendix 260 2CDC508134D0202 FCA S 1 x x 1 A 6 Notes ...
Страница 263: ......