3.3.2
Communication objects General
No.
Functionality
communication object name
Data type
Flags
0
In operation
General
1 bit
DPT 1.002
C, R, T
The communication object is enabled if the parameter
Enable communication object "In operation", 1-bit
has been selected
with the option
Send value 0/1 cyclically
In order to regularly monitor the presence of the device on the KNX, an in-operation monitoring telegram is sent cyclically on
the bus.
As long as the communication object is activated, it sends a programmable in operation telegram.
Telegram value:
1 = System in operation with option
Send value 1 cyclically
0 = System in operation with option
Send value 0 cyclically
1
Request status values
General
1 bit
DPT 1.017
C, W, T
This communication object is enabled if the parameter
Enable communication object "Request status values" 1-bit
has been
selected with the option
Yes
in
If the communication object receives a telegram with the value x (x = 0; 1; 0 or 1), all
Status
communication objects are sent
on the bus, as long as these have not been programmed with the option
On change, After request
or
After a change or
request
.
Option x = 1 produces the following function:
Telegram value:
1 = All status messages are sent
0 = No reaction
2
Block manual operation
General
1 bit
DPT 1.003
C, W
The communication object is enabled if the parameter
Manual operation
has been selected with the option
Enable/disable
via comm. object
Using this communication object the Manual operation is enabled or disabled.
Using the value 0, the button is blocked on the device. If the device is in
Manual operation
, it toggles immediately to
KNX
operation
.
Using the value 0, the button
is blocked on the device.
Telegram value:
1 =
button enabled
0 =
button disabled
3
Status Manual operation
General
1 bit
DPT 1.003
C, R, T
The communication object is enabled if the parameter
Enable communication object "Status Man. operation" (1-bit)
has
been selected with the option
Yes
This communication object indicates whether manual operation is activated.
The Status Manual operation is sent
On change
,
After request
or
After a change and request
as programmed.
Telegram value:
0 = Manual operation not active
1 = Manual operation active
Содержание i-bus KNX
Страница 1: ...ABB i bus KNX Fan Coil Actuators FCA S Product Manual ...
Страница 2: ......
Страница 6: ......
Страница 12: ......
Страница 24: ...ABB i bus KNX Device technology 22 2CDC508134D0202 FCA S 1 x x 1 2 1 12 Dimension drawing 2CDC072016F0013 ...
Страница 36: ...ABB i bus KNX Device technology 34 2CDC508134D0202 FCA S 1 x x 1 2 2 12 Dimension drawing 2CDC072031F0011 ...
Страница 48: ...ABB i bus KNX Device technology 46 2CDC508134D0202 FCA S 1 x x 1 2 3 11 Dimension drawing 2CDC072015F0013 ...
Страница 60: ...ABB i bus KNX Device technology 58 2CDC508134D0202 FCA S 1 x x 1 2 4 11 Dimension drawing 2CDC072015F0012 ...
Страница 262: ...ABB i bus KNX Appendix 260 2CDC508134D0202 FCA S 1 x x 1 A 6 Notes ...
Страница 263: ......