ABB i-bus
®
KNX
Commissioning
FCA/S 1.x.x.1 | 2CDC508134D0202 217
No.
Functionality
communication object name
Data type
Flags
51
Switch speed 1
Fan E, F, G
1 bit
DPT 1.001
C, W
This communication object is enabled if the parameter
Enable direct operation
has been selected with the option
Yes
in
Enable communication object "Switch speed x" 1-bit
has been selected with the option
Yes
in
Via the 1-bit communication object the device can receive a control value for fan speed 1.
Limitations through forced operation or one of the four limitations 1…4 are retained. Automatic operation is disabled.
communication object
Automatic ON/OFF
reactivates automatic operation.
If several ON telegrams are received consecutively in a short period of time at various
Switch speed x
(x = 1...3)
communication objects, the value last received is the one that will control the fan. An OFF telegram to one of the three
communication objects
Switch speed x
(x = 1...3) switches the fan off.
Telegram value:
0 = Fan OFF
1 = Fan ON in speed 1
52
Switch speed 2
See communication object 51
53
Switch speed 3
See communication object 51
54
Fan speed up/down
Fan E, F, G
1 bit
DPT 1.007
C, W
This communication object is enabled if the parameter
Enable direct operation
has been selected with the option
Yes
in
Enable communication object "Fan speed up/down"
1-bit
has been selected with the option
Yes
With this communication object, the fan can be switched one fan speed further up or down via a 1 bit telegram. Switching
(up/down) is determined by the telegram value.
With multiple manual up or down switching, the required speed will be increased or reduced by a speed step. This is feasible
until the maximum or minimum possible speed is reached. The parameterized limitations are taken into account here.
Further up or down telegrams are ignored and not executed. Each new switching telegram initiates a recalculation of the
required speed.
Telegram value:
0 = Switch fan speed DOWN
1 = Switch fan speed up
55
Status Fan ON/OFF
Fan E, F, G
1 bit
DPT 1.001
C, T
This communication object is enabled if the parameter
Enable communication object "Status Fan On/Off" 1-bit
has been
selected with the option
Yes
in
The communication object receives the communication object value 1 (ON), if at least one fan speed is not equal to zero
(OFF). The value of the communication object is sent if not equal to zero. This communication object thus defines the status
of the fan, whether it is switched on or off.
Telegram value:
0 = OFF
1 = ON
Note
Some fans require an ON telegram before you set a fan speed. Using the communication object
Status fan ON/OFF
,
the fan can, for example, be switched on centrally with a switch actuator via the main switch.
Содержание i-bus KNX
Страница 1: ...ABB i bus KNX Fan Coil Actuators FCA S Product Manual ...
Страница 2: ......
Страница 6: ......
Страница 12: ......
Страница 24: ...ABB i bus KNX Device technology 22 2CDC508134D0202 FCA S 1 x x 1 2 1 12 Dimension drawing 2CDC072016F0013 ...
Страница 36: ...ABB i bus KNX Device technology 34 2CDC508134D0202 FCA S 1 x x 1 2 2 12 Dimension drawing 2CDC072031F0011 ...
Страница 48: ...ABB i bus KNX Device technology 46 2CDC508134D0202 FCA S 1 x x 1 2 3 11 Dimension drawing 2CDC072015F0013 ...
Страница 60: ...ABB i bus KNX Device technology 58 2CDC508134D0202 FCA S 1 x x 1 2 4 11 Dimension drawing 2CDC072015F0012 ...
Страница 262: ...ABB i bus KNX Appendix 260 2CDC508134D0202 FCA S 1 x x 1 A 6 Notes ...
Страница 263: ......