ABB i-bus
®
KNX
Commissioning
164 2CDC508134D0202 | FCA/S 1.x.x.1
Object value "Switch" on
bus voltage recovery
Options:
Do not write
Write with "0"
Write with "1"
This parameter determines the reaction of the communication object
Switch
after a bus voltage recovery.
As standard the communication object
Switch
receives the value 0.
Don't write
: After bus voltage recovery, the value 0 is retained in the communication object
Switch
.
The switch state is not re-determined.
Note
Before the very first download (device fresh from the factory), the value before bus voltage failure is
undefined. For this reason, the communication object
Switch
is written with 0 and the contact is open.
Write with 0
: The communication object
Switch
is written with a 0 on bus voltage recovery. The
contact position is redefined and set based on the set device parameterization.
Write with 1
: The communication object
Switch
is written with a 1 on bus voltage recovery. The
contact position is redefined and set based on the set device parameterization.
Note
Take note of the reaction on bus voltage failure, recovery and download.
The device draws the energy for switching the contact from the bus. After bus voltage is applied, it takes
about ten seconds before sufficient energy is available to switch all contacts simultaneously.
Depending on the transmission and switching delay on bus voltage recovery set in the
General
parameter window, the individual outputs will only assume the desired contact position after this time.
If a shorter time is set, the device will only switch the first contact when sufficient energy is stored in the
device, in order to ensure that enough energy is available to immediately bring all outputs safely to the
required position if there is another bus voltage failure.
Enable function Time
Options:
No
Yes
No
: The parameter window remains disabled and invisible.
Yes
: The
- Time
parameter window appears.
After the
Time
function has been enabled, the parameter window
- Time
is enabled. Further settings are
undertaken there.
Note
For a more precise description of the function, see
Содержание i-bus KNX
Страница 1: ...ABB i bus KNX Fan Coil Actuators FCA S Product Manual ...
Страница 2: ......
Страница 6: ......
Страница 12: ......
Страница 24: ...ABB i bus KNX Device technology 22 2CDC508134D0202 FCA S 1 x x 1 2 1 12 Dimension drawing 2CDC072016F0013 ...
Страница 36: ...ABB i bus KNX Device technology 34 2CDC508134D0202 FCA S 1 x x 1 2 2 12 Dimension drawing 2CDC072031F0011 ...
Страница 48: ...ABB i bus KNX Device technology 46 2CDC508134D0202 FCA S 1 x x 1 2 3 11 Dimension drawing 2CDC072015F0013 ...
Страница 60: ...ABB i bus KNX Device technology 58 2CDC508134D0202 FCA S 1 x x 1 2 4 11 Dimension drawing 2CDC072015F0012 ...
Страница 262: ...ABB i bus KNX Appendix 260 2CDC508134D0202 FCA S 1 x x 1 A 6 Notes ...
Страница 263: ......