ABB i-bus
®
KNX
Commissioning
220 2CDC508134D0202 | FCA/S 1.x.x.1
No.
Functionality
communication object name
Data type
Flags
65
Forced operation
Fan E, F, G
1 bit
DPT 1.003
C, W
This communication object is enabled if the parameter
Enable communication object "Forced operation" 1-bit
has been
selected with the option
Yes
in
If a forced operation is activated, the device switches to forced operation regardless of the control value and its
parameterized Limitation 1...4.
Telegram value:
0 = No forced operation
1 = Forced operation
66
Automatic ON/OFF
Fan E, F, G
1 bit
DPT 1.003
C, W
This communication object is enabled if
Automatic operation
has been enabled in
If automatic operation is enabled, it will be activated after a download, an ETS reset or by an ON telegram on this
communication object.
Automatic mode is switched off if a telegram is received on a "manual communication object".
Manual communication objects are:
Fan: Switch speed
Fan: Switch speed x (x = 1, 2 or 3)
Fan: Fan speed up/down
Fan: Limitation x (x = 1, 2, 3 or 4)
During forced operation, automatic mode remains active but operates only within the allowed limits.
If the value 1 is set in the parameter:
Telegram value:
0 = Automatic operation OFF
1 = Automatic operation ON
If the value 0 is set in the parameter:
Telegram value:
0 = Automatic operation ON
1 = Automatic operation OFF
67
Status Automatic
Fan E, F, G
1 bit
DPT 1.003
C, R, T
This communication object is enabled if the parameter
Enable communication object "Status Automatic" 1-bit
has been
selected with the option
Yes
in
You can parameterize whether the communication object value is updated but not sent, sent on request, or only sent when
changed.
The communication object indicates the status of automatic operation.
Telegram value:
0 = Inactive
1 = Activated
Содержание i-bus KNX
Страница 1: ...ABB i bus KNX Fan Coil Actuators FCA S Product Manual ...
Страница 2: ......
Страница 6: ......
Страница 12: ......
Страница 24: ...ABB i bus KNX Device technology 22 2CDC508134D0202 FCA S 1 x x 1 2 1 12 Dimension drawing 2CDC072016F0013 ...
Страница 36: ...ABB i bus KNX Device technology 34 2CDC508134D0202 FCA S 1 x x 1 2 2 12 Dimension drawing 2CDC072031F0011 ...
Страница 48: ...ABB i bus KNX Device technology 46 2CDC508134D0202 FCA S 1 x x 1 2 3 11 Dimension drawing 2CDC072015F0013 ...
Страница 60: ...ABB i bus KNX Device technology 58 2CDC508134D0202 FCA S 1 x x 1 2 4 11 Dimension drawing 2CDC072015F0012 ...
Страница 262: ...ABB i bus KNX Appendix 260 2CDC508134D0202 FCA S 1 x x 1 A 6 Notes ...
Страница 263: ......