ABB i-bus
®
KNX
Commissioning
144 2CDC508134D0202 | FCA/S 1.x.x.1
Enable communication object
"Fan speed up/down" 1-bit
Options:
Yes
No
Yes
: A 1 bit
Fan speed up/down
communication object is enabled.
Telegram
value:
1 = A fan speed is switched UP
0 = A fan speed is switched DOWN
If the maximum fan speed is reached and a further telegram with the value 1 is received, the speed will
remain as it is.
Important
Forced operation remains valid and is taken into account.
The parameterized minimum fan speed dwell time for automatic control is ignored during manual
operation. Accordingly, an immediate reaction to manual operation is detected.
The delay time with speed switchover remains active to protect the fan.
With multiple manual UP or DOWN switching, the required speed will be increased or reduced by a speed
step. This is feasible until the maximum or minimum possible speed is reached. Further UP or DOWN
telegrams are ignored and not executed. Each new switching telegram initiates a new calculation of the
target speed. This means that the target speed can be changed by switching telegrams until the target
speed is achieved.
Enable communication object
"Switch speed" 1-byte
Options:
Yes
No
Selection of option
Yes:
Dependent parameter:
Options:
DPT 5.001
DPT 5.010
DPT 5.001:
The 1-byte communication object
Switch speed
(in percent)
is enabled.
DPT 5.010
: The 1-byte communication object
Switch speed
(counting pulse) is enabled.
With this parameter the DPT used to switch the fan speed is set.
Содержание i-bus KNX
Страница 1: ...ABB i bus KNX Fan Coil Actuators FCA S Product Manual ...
Страница 2: ......
Страница 6: ......
Страница 12: ......
Страница 24: ...ABB i bus KNX Device technology 22 2CDC508134D0202 FCA S 1 x x 1 2 1 12 Dimension drawing 2CDC072016F0013 ...
Страница 36: ...ABB i bus KNX Device technology 34 2CDC508134D0202 FCA S 1 x x 1 2 2 12 Dimension drawing 2CDC072031F0011 ...
Страница 48: ...ABB i bus KNX Device technology 46 2CDC508134D0202 FCA S 1 x x 1 2 3 11 Dimension drawing 2CDC072015F0013 ...
Страница 60: ...ABB i bus KNX Device technology 58 2CDC508134D0202 FCA S 1 x x 1 2 4 11 Dimension drawing 2CDC072015F0012 ...
Страница 262: ...ABB i bus KNX Appendix 260 2CDC508134D0202 FCA S 1 x x 1 A 6 Notes ...
Страница 263: ......