ABB i-bus
®
KNX
Commissioning
FCA/S 1.x.x.1 | 2CDC508134D0202 175
Scan input after download,
ETS reset and bus voltage recovery
Options:
No
Yes
No:
The object value is not scanned after a download, ETS reset and bus voltage recovery.
Yes:
The object value is scanned after a download, ETS reset and bus voltage recovery.
Dependent parameter:
Inactive wait state after bus voltage
recovery in s [0…65,535]
Options:
0
…65,535
Here the waiting time after a bus voltage recovery is set. After the waiting time has elapsed the
state on the input terminals is scanned. The input reacts as if the state on the input terminals has
just changed.
Note
The inactive waiting time does not add to the actual, adjustable sending delay time. This can be
set separately.
Enable communication object
"Start event 0/1" 1-bit
Options:
Yes
No
Yes:
The 1-bit communication object
Start event 0/1
is enabled. As a result, the same events, such as
those of the push button/switch connected to the binary input, can also be triggered by the receipt of a
telegram on the communication object
Start event 0/1
.
Enable communication object
"Block" 1-bit
Options:
No
Yes
Yes:
The 1-bit block communication object
Block
is enabled. This can be used to disable the input.
Notes
If the input is disabled and the option
Send cyclically
is set, the last state is still sent regardless of the
block. The option
Block
still blocks the physical input, sending continues internally.
Should the internal block with this input not be permitted, this communication object has no effect on the
respective input.
Содержание i-bus KNX
Страница 1: ...ABB i bus KNX Fan Coil Actuators FCA S Product Manual ...
Страница 2: ......
Страница 6: ......
Страница 12: ......
Страница 24: ...ABB i bus KNX Device technology 22 2CDC508134D0202 FCA S 1 x x 1 2 1 12 Dimension drawing 2CDC072016F0013 ...
Страница 36: ...ABB i bus KNX Device technology 34 2CDC508134D0202 FCA S 1 x x 1 2 2 12 Dimension drawing 2CDC072031F0011 ...
Страница 48: ...ABB i bus KNX Device technology 46 2CDC508134D0202 FCA S 1 x x 1 2 3 11 Dimension drawing 2CDC072015F0013 ...
Страница 60: ...ABB i bus KNX Device technology 58 2CDC508134D0202 FCA S 1 x x 1 2 4 11 Dimension drawing 2CDC072015F0012 ...
Страница 262: ...ABB i bus KNX Appendix 260 2CDC508134D0202 FCA S 1 x x 1 A 6 Notes ...
Страница 263: ......