ABB i-bus
®
KNX
Commissioning
FCA/S 1.x.x.1 | 2CDC508134D0202 111
Valve is
Options:
Heating valve
Cooling valve
This parameter determines whether the valve is defined as a heating valve or cooling valve.
Monitoring control values
e.g. thermostat
Options:
No
Yes
This parameter is activated for monitoring cyclic sending of the control value, e.g. of the room thermostat.
The reaction to the absence of a control value is defined in monitoring of the control value. This ensures
emergency operation.
Yes:
The communication object
p. 211, is enabled.
Dependent parameters:
Monitoring time
in s [30…65,535]
Options:
30…120…65,535
This parameter sets the time used to monitor the telegrams on the input control values:
communication objects
Control value, ON/OFF
, if the option
Bit
has been selected for the
parameter
Control value is received as
, or
Control value, continuous (PWM) 1
, if the option
Byte
has been selected for the parameter
Control value is received as
.
If a control value is not received within the parameterized time, a malfunction or a defective room
thermostat is the cause.
The reaction of the output to a control value not received can be defined in the following
parameters.
Send object value "Control value fault"
Options:
No, update only
On change
After request
After a change or request
No, update only
: The object value is updated but not sent.
On change
: The object value is sent when a change occurs.
After request
: The object value is sent when a request occurs.
After a change or request
: The object value is sent when a change or request occurs.
Содержание i-bus KNX
Страница 1: ...ABB i bus KNX Fan Coil Actuators FCA S Product Manual ...
Страница 2: ......
Страница 6: ......
Страница 12: ......
Страница 24: ...ABB i bus KNX Device technology 22 2CDC508134D0202 FCA S 1 x x 1 2 1 12 Dimension drawing 2CDC072016F0013 ...
Страница 36: ...ABB i bus KNX Device technology 34 2CDC508134D0202 FCA S 1 x x 1 2 2 12 Dimension drawing 2CDC072031F0011 ...
Страница 48: ...ABB i bus KNX Device technology 46 2CDC508134D0202 FCA S 1 x x 1 2 3 11 Dimension drawing 2CDC072015F0013 ...
Страница 60: ...ABB i bus KNX Device technology 58 2CDC508134D0202 FCA S 1 x x 1 2 4 11 Dimension drawing 2CDC072015F0012 ...
Страница 262: ...ABB i bus KNX Appendix 260 2CDC508134D0202 FCA S 1 x x 1 A 6 Notes ...
Страница 263: ......