ABB i-bus
®
KNX
Commissioning
FCA/S 1.x.x.1 | 2CDC508134D0202 197
3.2.4.4.3
Line fault compensation
Via cable length:
Cable length, single distance
[1...30 m]
Options:
1...10...30
For setting the single cable length of the connected temperature sensor.
Important
The maximum cable length permitted between the sensor and device input is 30 m.
Cross-section of conductor
Value * 0.01 mm
2
[1...150]
Options:
1...100...150 (150 = 1.5 mm
2
)
The cross-section of the conductor to which the temperature sensor is connected is entered using this
parameter.
Important
Line fault compensation via cable length is only suitable for copper conductors.