238 2CDC508134D0202 | FCA/S 1.x.x.1
4.1
Fan output
In this section, the function charts and application explanations for the fan outputs are explained.
4.1.1
Fan operation
In fan operation a single phase fan, blower or convector can be controlled. In combination with a valve
control 2, 3 or 4 pipe system can be implemented. The fans are controlled via a 3 stage speed controller.
For this purpose, three windings are tapped off the fan motor. The resulting fan speed is dependent on the
tapping selected. It must be ensured that two contacts are not switched on simultaneously. For control
purposes, at least one 3 stage changeover switch with zero position is usually used. This switch is mapped
with a group of outputs in the device.