222 2CDC508134D0202 | FCA/S 1.x.x.1
No.
Functionality
communication object name
Data type
Flags
69
Control value A
(if 2 control values) or
Control value
(if only 1 control value)
Fan E, F, G
1 byte
DPT 5.010
C, W
This communication object is enabled if
Automatic operation
has been enabled in
Using this communication object, the control value for automatic operation is predefined as a 1-byte value [0...255].
70
Control value B
(if 2 control values)
Fan E, F, G
1 byte
DPT 5.010
C, W
This communication object is enabled if automatic operation has been enabled in
, p. 124, and two inputs have been activated by the parameter
Number of control value inputs
Using this communication object the second control value for automatic operation is predefined as a 1 byte value [0...255].
71
Toggle control value A/B
(if 2 control values)
Fan E, F, G
1 bit
DPT 1.001
C, W
This communication object is enabled if two communication objects have been activated for the control values (control value
A and control value B) in
, p. 137, and they are to be selected by a
communication object.
72
Fault control value
Fan E, F, G
1 bit
DPT 1.005
C, R, T
This communication object is enabled if the parameter
Activate monitoring control values
has been selected with the option
Yes
This communication object displays control value faults.
The blower actuator uses the
Fault control value
communication object to report a fault and then reacts according to the
parameterization for faults.
Telegram value:
0 = No fault
1 = Fault
Note
If no value is sent to the communication object
Control value A,
Control value B
or
Control Value
for a set time, a
sender fault is assumed. If the communication object
Toggle control value A/B
receives a value, the monitoring time
is started.
73…79
Not assigned
Содержание i-bus KNX
Страница 1: ...ABB i bus KNX Fan Coil Actuators FCA S Product Manual ...
Страница 2: ......
Страница 6: ......
Страница 12: ......
Страница 24: ...ABB i bus KNX Device technology 22 2CDC508134D0202 FCA S 1 x x 1 2 1 12 Dimension drawing 2CDC072016F0013 ...
Страница 36: ...ABB i bus KNX Device technology 34 2CDC508134D0202 FCA S 1 x x 1 2 2 12 Dimension drawing 2CDC072031F0011 ...
Страница 48: ...ABB i bus KNX Device technology 46 2CDC508134D0202 FCA S 1 x x 1 2 3 11 Dimension drawing 2CDC072015F0013 ...
Страница 60: ...ABB i bus KNX Device technology 58 2CDC508134D0202 FCA S 1 x x 1 2 4 11 Dimension drawing 2CDC072015F0012 ...
Страница 262: ...ABB i bus KNX Appendix 260 2CDC508134D0202 FCA S 1 x x 1 A 6 Notes ...
Страница 263: ......