ABB Distribution Protection Unit 1500R
8-2
Monitoring and Control
9/99
website:www.abb.com/papd
Metering Status
The present values of Load, Demand, and
Min/Max Demand metering can be viewed
in real-time with WinECP and through the
front-panel MMI. Use the Monitoring Menu
in Win ECP, and the Meter Menu on the
front-panel MMI. See Section 3 for more
information.
Logical Output Status
The logical output status shown in Figure
8-3 displays which output functions are
energized and de-energized. Use this
display to confirm whether or not the
functions are programmed correctly in the
Pr imar y, Alter nate 1, Alter nate 2,
Programmable Inputs and Alarm Settings
tables. Also use it to check that the
settings provide the desired results. This
feature is not available through the
front-panel MMI.
Forcing I/O
To aid in DPU1500R commissioning and testing, the state of all Physical Inputs and Outputs, and Logical Inputs can be
forced through WinECP or front-panel MMI. This feature can be accessed in WinECP through the Control Menu, and
through front-panel MMI through the Operations Menu. When one or more input/output is in the forced condition the
“Normal” LED on front panel will blink on and off. All forcing of I/O is password protected. See Figures 8-4 through 8-6.
Figure 8-4. Forcing Physical Inputs
Figure 8-3. Logical Output Status