ABB Distribution Protection Unit 1500R
7-12
Records
9/99
website:www.abb.com/papd
Ext Trip Enabled
Indicates that the programmable input “Open” was asserted. This record indicates the state of the
programmable input “Open” only. It does not imply an actual breaker trip.
Ext Trip Disabled
Indicates that the programmable input “Open” was de-asserted.
Event Cap 1 Init
Indicates that the programmable input “ECI1” was asserted and an event capture taken. The data
from the event is stored in the Fault Records.
Event Cap 1 Reset
Indicates that the programmable input “ECI1” was de-asserted.
Event Cap 2 Init
Indicates that the programmable input “ECI2” was asserted and an event capture taken. The data
from the event is stored in the Fault Records.
Event Cap 2 Reset
Indicates that the programmable input “ECI2” was de-asserted.
Wave Cap Init
Indicates that the programmable input “WCI” was asserted and an oscillographic record stored. The
data from the event is stored in the Waveform Capture Records.
Wave Cap Reset
Indicates that the programmable input “WCI” was de-asserted.
Ext Close Enabled
Indicates that the programmable input “Close” was asserted. This record indicates the state of the
programmable input “Close” only. It does not imply an actual breaker close.
Ext Close Disabled
Indicates that the programmable input “Close” was de-asserted.
52a Closed
Indicates the state of the programmable logic input “52A”. This record indicates the state of the
programmable input “52A” only. It does not imply an actual breaker state. The “52A Closed” record
indicates that the “52A” logical input was at a logical 1 at the time of the logging.
52a Opened
Indicates the state of the programmable logic input “52A”. This record indicates the state of the
programmable input “52A” only. It does not imply an actual breaker state. The “52A Opened” record
indicates that the “52A” logical input was at a logical 0 at the time of the logging.
52b Closed
Indicates the state of the programmable logic input “52B”. This record indicates the state of the
programmable input “52B” only. It does not imply an actual breaker state. The “52B Closed” record
indicates that the “52B” logical input was at a logical 1 at the time of the logging.
52b Opened
Indicates the state of the programmable logic input “52B”. This record indicates the state of the
programmable input “52B” only. It does not imply an actual breaker state. The “52B Opened” record
indicates that the “52B” logical input was at a logical 0 at the time of the logging.
46 Unit Enabled
Indicates that the programmable input, “46” transitioned from a logical 0 to a logical 1, enabling the
negative sequence time overcurrent element if used. This log indicates the state of the “46” input
only.
46 Unit Disabled
Indicates that the programmable input, “46” transitioned from a logical 1 to a logical 0, disabling the
negative sequence time overcurrent element if used. This log indicates the state of the “46” input
only.
CRI Input Closed
Indicates that the programmable input Clear Reclose and Overcurrent Counters, “CRI”, transitioned
from a logical 0 to a logical 1. See Section 6, specifically the “CRI” input, for more details.
CRI Input Opened
Indicates that the programmable input Clear Reclose and Overcurrent Counters, “CRI”, transitioned
Table 7-2 (cont.)
(
XO
)
(
XO
)
(
XI
)
(
XI
)
(
Insc>
)
(
Insc>
)