ABB Distribution Protection Unit 1500R
7-10
Records
9/99
website:www.abb.com/papd
Blown Fuse Alarm
Indicates that “BFUA” programmable logical output has operated. See the Programmable Outputs
Section specifically the “BFUA” output for more details.
OC Trip Counter
Indicates that the Overcurrent Trip Counter has exceeded the Overcurrent Trip Counter Alarm setting.
See Section 6, specifically the “OCTC” output, for more details.
Accumulated KSI
Indicates that the KSI summation has exceeded the KSI Alarm setting. See Section 6, specifically the
“KSI” output, for more details.
79 Counter 1 Alarm
Indicates that the number of reclose operations has exceeded the Reclose Counter 1 Alarm setting. See
Section 6, specifically the “79CA1” output, for more details.
Phase Demand Alarm
Indicates that the phase demand current has exceeded the Phase Demand Current Alarm setting. See
Section 6, specifically the “PDA” output, for more details.
Neutral Demand Alarm
Indicates that the neutral demand current has exceeded the Neutral Demand Current Alarm setting. See
Section 6, specifically the “NDA” output, for more details.
Low PF Alarm
Indicates that the power factor has gone below the Low Power Factor Alarm setting. See the Section
6, specifically the “LPFA” output, for more details.
High PF Alarm
Indicates that the power factor has risen above the High Power Factor Alarm setting. See Section 6,
specifically the “HPFA” output, for more details.
Trip Coil Failure
Indicates that the logical input “TCM” indicated a trip coil failure. See Section 6, specifically the “TCM”
input.
KVAr Demand Alarm
Indicates that the demand KiloVArs have exceeded the Demand KiloVAr Alarm setting. See Section 6,
specifically the “VARDA” output, for more details.
79 Counter 2 Alarm
Indicates that the number of reclose operations has exceeded the Reclose Counter 2 Alarm setting. See
Section 6, specifically the “79CA2” output, for more details.
Pos. KVAr Alarm
Indicates that the positive KiloVArs have exceeded the Positive KiloVAr Alarm setting. See Section 6,
specifically the “PVArA” output, for more details.
Neg. KVAr Alarm
Indicates that the negative KiloVArs have exceeded the negative KiloVAr Alarm setting. See Section 6,
specifically the “NVArA” output, for more details.
Load Alarm
Indicates that the load current has exceeded the Load Current Alarm setting. See Section 6, specifically
the “LOADA” output, for more details.
Cold Load Alarm
Logs when the cold load timer is counting down. Also see CLTA logical output description.
Pos Watt Alarm 1
Indicates that the positive kilowatts have exceeded the Positive Kilowatt Alarm 1 setting. See Section
6, specifically the “Pwatt1” output, for more details.
Pos Watt Alarm 2
Indicates that the positive kilowatts have exceeded the Positive Kilowatt Alarm 2 setting. See Section
6, specifically the “Pwatt2” output, for more details.
BFT Operation
Indicates operation of the Breaker Failure Trip (BFT) logical output.
ReTrip Operation
Indicates operation of the ReTrip logical output.
Table 7-2 (cont.)
(
O->I-1
)
(
O->I-2
)