ABB Distribution Protection Unit 1500R
5-22
Interfacing with the Relay
website:www.abb.com/papd
9/99
Table 5-3. Counter Settings (Password Protected)
Table 5-4. Alarm Settings (Password Protected)
In the Counter Settings Menu, the user has the option to change the value of the various counters.
In the Alarm Settings Menu, the user has the option to set thresholds for various alarms. When the threshold is
exceeded, the corresponding logical output is asserted. (See “Programmable I/O” Section).
Setting
Range
Step Size
Default
KSI Summation A Phase Setting - KSI Sum A (L1)
0 to 9999 kA
1
0
KSI Summation B Phase Setting - KSI Sum B (L2)
0 to 9999 kA
1
0
KSI Summation C Phase Setting - KSI SumC (L3)
0 to 9999 kA
1
0
Overcurrent Trip Counter
0 to 9999
1
0
Breaker Operations Counter
0 to 9999
1
0
79 (O->I) Counter 1
0 to 9999
1
0
0 to 9999
1
0
1st Reclose Counter (1st Recl) [successful]
0 to 9999
1
0
0 to 9999
1
0
0 to 9999
1
0
0 to 9999
1
0
79 (O->i) Counter 2
2st Reclose Counter (2nd Recl) [successful]
3rd Reclose Counter (3rd Recl) [successful]
4th Reclose Counter (4th Recl) [successful]
Setting
Range
Step Size
Default
KSI Summation
1 to 9999 (kA)
1
Disable
Over Current Trip Counter
1 to 9999
1
Disable
79 (O->I) Counter 1
1 to 9999
1
Disable
79 (O->I) Counter 2
1 to 9999
1
Disable
Phase Demand Current Alarm
1 to 9999 (A)
1
Disable
Neutral Demand
1 to 9999 (A)
1
Disable
Demand 3P-kVar [3-phase kilo VAr alarm]
(Dmnd 3P-kVAr)
10 to 99,990 (kVAr)
10
Disable
10 to 99,990 (kVAr)
10
Disable
Negative kVAr [3-phase KiloVAr alarm]
10 to 99,990 (kVAr)
10
Disable
Low PF [power factor alarm]
0.5 to 1.0 (lagging)
0.01
Disable
High PF [power factor alarm]
0.5 to 1.0 (lagging)
0.01
Disable
Load Current [alarm]
1 to 9999 (A)
1
Disable
Positive kVAr [3-phase kiloVAr alarm]
Positive KWatt Alarm 1
Disable
Disable
1
1
1 to 9999
1 to 9999
Positive KWatt Alarm 2
Logical Output
KSI
OCTC
79CA1
79CA2
PDA
NDA
VarDA
LPFA
HPFA
LOADA
PVArA
NVArA
PWatt1
PWatt2