ABB Distribution Protection Unit 1500R
5-20
Interfacing with the Relay
website:www.abb.com/papd
9/99
Setting
Range
Step Size
Default
Function
50N-3
Selection
Disable or Enable
Disable
Pickup X 51N
0.5 to 20 times
51N pickup setting
0.1
-
79
Reset Time
3 to 200 seconds
1
10.00
79-1
Select
50P-1, 50P-2, 50P-3, 51N, 50N-1, 50N-2,
50N-3 (Enable, Disable, or Lockout for each)
Open Time
0.1 to 200 seconds or Lockout
Lockout
0.1
50-P Enable
51-N Enable
50N-1 Enable
50N-2
⊗
Select
Disable, Standard, SEF, Directional SEF
Disable
SEF Pickup Amps
⊗
0.005 to 0.200 A
0.0005
-
Delay
⊗
0.5 to 180.0 seconds
0.1
-
Torque Angle*
0 to 355
5
-
⊗
SEF Model
* Directional SEF Model Only
79-2
50P-1, 50P-2, 50P-3, 51N, 50N-1, 50N-2,
50N-3 (Enable, Disable, or Lockout for each)
-
Open Time
0.1 to 200 seconds or Lockout
-
79-3
50P-1, 50P-2, 50P-3, 51N, 50N-1, 50N-2,
50N-3 (Enable, Disable, or Lockout for each)
-
Open Time
0.1 to 200 seconds or Lockout
-
79-4
50P-1, 50P-2, 50P-3, 51N, 50N-1, 50N-2,
50N-3 (Enable, Disable, or Lockout for each)
-
Open Time
0.1 to 200 seconds or Lockout
-
79-5
50P-1, 50P-2, 50P-3, 51N, 50N-1, 50N-2,
50N-3 (Enable, Disable, or Lockout for each)
-
-
79-CO (O->I-CO)
Cutout Time
1 to 200 seconds or Disable
1
Disable
Cold Load Time
0 to 254 seconds/minutes or Disable
1
Disable
2-Phase 50P
2Phase 50P Trip
Disable or Enable
Disable
0.1
0.1
0.1
Select
Select
Select
Select
Open Time
Lockout
27
79V
Select
Disable or Enable
Disable
Pickup Volts
10 to 200 volts AC
1
-
Time Delay
0 to 60 seconds
1
-
Voltage Select
Disable or Enable
Pickup Volts
10 to 200 volts AC
1
-
Time Delay
4 to 200 seconds
1
-
(IN>>3)
(O->I)
(O->I1)
(O->I2)
(O->I3)
(O->I4)
(O->I5)
(3I>>)
(U<)
(O->IU<)
(IO
/
>)
Table 5-1. Primary, Alternate 1 and Alternate 2 Settings (Password Protected) (Continued)