ABB Distribution Protection Unit 1500R
2-4
Configuration Settings
9/99
website:www.abb.com/papd
Remote Edit
“Enable” allows settings to be changed via the communication ports.
“Disable” disallows setting changes via the communication ports.
This setting can only be changed locally through the MMI.
Meter Mode
Select KWHr or MWHr for kilowatt/kilovar or Megawatt/Megavar metering.
LCD Light
Select “ON” for continuous display.
Select “TIME OUT” to enable the LCD Screen saver. This setting will significantly extend the life of the LCD display.
After the Screen saver times out, the user can press any button to activate the LCD display.
Unit ID
Type a 15 character description of the relay.
Demand Meter Constant
Select 5, 15, 30 or 60 minute time constant. Demand currents replicate thermal demand meters. The demand
kilowatts and kiloVArs are averaged values that are calculated by using the kilowatt-hours, kiloVArs-hours and the
selected time constant.
LCD Contrast
This setting adjusts the brightness of the LCD Display. Adjustable from 0-63. The DPU1500R LCD automatically
compensates for change in temperature reducing the need to adjust the default contrast setting for improved legibility.
Change Relay Password
The relay password can be changed via the MMI in the configuration settings menu. Using ECP, the user can change
the relay password when exiting out of the configuration settings menu, select “send settings to unit”, and select “Yes”
to change relay password.
Change Test Password
The test password allows access to the actions in the Test Menu and the Operations Menu, see Section 6. The user
cannot make setting changes with the test password.