53
Accessories
3ADW000379R0501 DCS550 Manual e e
Line reactor types ND401 to ND413 (u
k
= 4 %)
Line reactors of types ND401 to ND413 are sized to the unit’s nominal current and frequency (50 / 60 Hz).
These line reactors with a u
k
of 4 are designed for use in light industrial / residential environment. They have
high inductive voltage drop, but reduced commutation notches. These reactors are designed for drives, which
usually operate in speed control in 400 or 500 V
AC
networks. The percentage taken into account for that duty
cycle is different:
−
for U
supply
= 400 V
AC
follows I
DC1
= 90 % of nominal current,
−
for U
supply
= 500 V
AC
follows I
DC2
= 72 % of nominal current.
Line reactors ND401 to ND402 are equipped with terminals. The larger ones ND403 to ND413 are equipped
with busbars. When connecting them to other components, please consider relevant standards in case the
busbar materials are different.
Attention:
Do not use the line reactor terminals as cable or busbar support!
Size Converter type (2-Q) Converter type (4-Q) Line reactor (u
k
= 4 %) Design figure
F1
DCS550-S01-0020
DCS550-S02-0025
ND401
4
DCS550-S01-0045
DCS550-S02-0050
ND402
DCS550-S01-0065
DCS550-S02-0075
ND403
5
DCS550-S01-0090
DCS550-S02-0100
ND404
F2
DCS550-S01-0135
DCS550-S02-0150
ND405
DCS550-S01-0180
DCS550-S02-0200
ND406
DCS550-S01-0225
DCS550-S02-0250
ND407
DCS550-S01-0270
DCS550-S02-0300
ND408
F3
DCS550-S01-0315
DCS550-S02-0350
DCS550-S01-0405
DCS550-S02-0450
ND409
DCS550-S01-0470
DCS550-S02-0520
ND410
F4
DCS550-S01-0610
DCS550-S02-0680
ND411
DCS550-S01-0740
DCS550-S02-0820
ND412
DCS550-S01-0900
DCS550-S02-1000
ND413
Fig. 5
Fig. 4
Содержание DCS550 Series
Страница 1: ... DCS550 Manual DCS550 Drives 20 A to 1000 A ...
Страница 141: ...141 Winder 3ADW000379R0501 DCS550 Manual e e ...
Страница 143: ...143 Winder 3ADW000379R0501 DCS550 Manual e e ...
Страница 145: ...145 Winder 3ADW000379R0501 DCS550 Manual e e ...
Страница 147: ...147 Winder 3ADW000379R0501 DCS550 Manual e e ...